Descargar Imprimir esta página

Hisense AVD-07H3FH Manual De Instalación, Funcionamiento Y Mantenimiento página 22

Publicidad

Idiomas disponibles

Idiomas disponibles

(1) DIP switch must be set with power sources of the indoor
and outdoor units in OFF state. Otherwise, the settings are
invalid.
(2) The location of DIP switch is shown in the figure below.
(3) The PCB of indoor unit is furnished with 5 DIP switches
that must be set based on the following requirements
before test run. The system must not be started before
the completion of DIP setup.
All indoor units must be numbered (DSW6) as shown
(a)
in the figure below. The outdoor unit numbering must
start with "0".
DSW6(Setting 0~63)
DSW6 are set to "0" before delivery. 64 indoor units
can be connected.
Remarks: For DSW6 six-bit binary 8421 code, see
the comparison table on the next page.
(b) Capacity Code Setting (DSW3)
No setup is required.
The code is set before delivery. This switch is used to
set the capacity of indoor unit.
(c) Model Code Setting (DSW4)
No setup is required. The code is set before delivery.
Default No.1 and 3 ON.
(d) Cooling System Code No. Setting (DSW5)
The setup is needed. All are set to OFF before delivery.
9
Ex.)Set machine No.16
No.5 ON
16
Refrigerant System Setting
DSW5(Setting 0~63)
DSW5 are set to "0" before delivery. 64 indoor units can be
connected.
Remarks: For DSW5 six-bit binary 8421 code, see
the comparison table on the next page.
(e) Other function setting (DSW9)
No setup is required. The code is set before delivery.
Model
AVD-24H3FH1
Setting
Position
Note:
Symbol "■" indicates the location of DIP switch.
The position indicated in the diagram is in the factory-set
state.
The power supply shall be turned off before the setup of
DIP switch. Otherwise, the settings will be invalid.
Ex.) Set system No. 5
Other models

Publicidad

loading