PSU67-3P-1S-2L-24250-F
EN
Quick Start Guide
If an external fuse is used, use B or C characteristic circuit breakers with at
➤
least 6 A to avoid a nuisance tripping of the circuit breaker.
When connecting capacitors with capacitance >20 mF to an output, this
output may be switched off after switching on the device or the output or
connecting the load.
Operating
CAUTION
Hot surfaces
Burn risk
Do not touch the housing during operation or shortly after power-off.
➤
The green Status LED reports an output above 90 % of the set output voltage.
The device is safe in case of a single phase loss. An external protection is
not necessary. A disconnecting means shall be provided for the input of the
device.
Relay-OK contact
The Relay OK contact monitors the output voltage. If the contact is closed,
the Status LED green lights up green
Contact ratings:
■
60 VDC, 0.3 A
■
30 VDC, 1 A
■
30 VAC, 0.5 A for resistive loads
LED bar and push-buttons
■
Monitoring mode (normal operation):
Actual output power = percentage of 500 W (100 % = 500 W)
For values above 100 %, the LEDs flash orange. By pressing the up and down
keys, the output current of the respective output is displayed as a percentage
of the set tripping current.
The orange LEDs OUT1 and OUT2 indicate the selected output.
■
Configuration mode
Button [Voltage Set]
Hold for 3 s Configuration mode, all LEDs flash shortly.
Start mode: "Set output voltage": The output voltage is set for all outputs.
All orange LEDs are off.
Hold for 3 s,
Mode "Set tripping current": The tripping current (s. fig. 4) is set separately
press 1×
for each output. The orange LEDs OUT1 and OUT2 indicate the selected
output.
Hold for 3 s,
Select other output, n = no. of output
press n ×
(only for „set tripping current")
Buttons [] []
Set value
The set value for output voltage or tripping current is indicated via the LED
bar. The setting becomes effective immediately.
After 15 s without pressing the buttons, the LED bar switches back to normal
operation.
Hans Turck GmbH & Co. KG | Witzlebenstraße 7, 45472 Mülheim an der Ruhr, Germany | Tel. +49 208 4952-0 | Fax +49 208 4952-264 | more@turck.com | www.turck.com
Deactivating outputs
Press the button at the output channel (OUT1 or OUT2) for at least 1 s to
➤
activate or deactivate the output manually.
Maintenance
Clean the devices at regular intervals with a damp cloth.
Repair
The device must not be repaired by the user. Take defective devices out of
operation. Observe our return acceptance conditions when returning the
device to Turck.
Disposal
The devices must be disposed of correctly and must not be included in
normal household garbage.
Technical data
All values are typical figures specified at 3 × 400 VAC, 50 Hz input voltage, symmetrical
phase voltages, 24 V, 500 W output load, 25 °C ambient temperature and after a 5 min-
utes run-in time unless specified otherwise.
Device
Type designation
PSU67-3P-1S-2L-24250-F
ID
100028238
Outputs
Output voltage
24 VDC, nominal value
Adjustment range
24...28 VDC
Output power, 24...28 V, continuous at ambient temperature:
– at 45 °C
570...600 W
– at 55 °C
500... 500 W
– at 70 °C
350...350 W
Linear derating between +45 °C and +70 °C (s. fig. 5)
Output currents
Up to 12 A, settable per output
Input
Input voltage AC
3 AC, 380... 480 V ±15 %
Mains frequency
50...60 Hz ±6 %
Input current AC
0.8/0.66 A at 3 × 400/480 VAC
Power factor
0.94/ 0.95 at 3 × 400/480 VAC
Wiring diagrams
v
1 = L1
4
FE
2 = L2
4
1
3 = L3
1
3
4 = PE
3
2
2
Input M12 (XD1)
Output M12 (XD2, XD3)
1 = RELAY +
1
2 = n.c.
4
2
3 = n.c.
4 = RELAY -
5
3
5 = n.c.
Relay-OK M12 (X0)
Input inrush current
1.9/1.8 A peak at 3 × 400/480 VAC, temp.
independent
Efficiency
Efficiency
95.8/95.6 % at 3 × 400/480 VAC
Losses
20.8/23.0 W at 3 × 400/480 VAC
Hold-up time
24/24 ms at 3 × 400/480 VAC
Ambient conditions
Temperature range
-25...+70 °C
Max. operating temperature
+70 °C, measured 2 cm below the device
Relative humidity
5...95 %
Housing
Dimensions (l × w × h)
183 × 182 × 59 mm, without connectors
Weight
1200 g/2.7 lb
Degree of protection
IP65/IP67, with all mating connectors
(according to IEC 60529)
firmly connected
Protection against electrical, mechanical
and fire hazards
© Hans Turck GmbH & Co. KG | 100032473 2023-06
1 = 24 VDC (V1)
2 = GND (V2)
3 = GND (V1)
4 = 24 VDC (V2)
FE