10 Attachment
■
Single-Phase 200 V Class
Table 10.9 Factory-Recommended Branch Circuit Protection: Single-Phase 200 V Class
Maximum Applicable Motor
Drive Model
B001
B002
B004
B006
B010
B012
B018
■
Three-Phase 400 V Class
Table 10.10 Factory-Recommended Branch Circuit Protection: Three-Phase 400 V Class
Maximum Applicable Motor
Drive Model
4001
4002
4004
4005
4007
4009
4012
4018
4023
4031
4038
282
Output
kW (HP)
ND
HD
0.18 (1/6)
0.1 (1/6)
0.37 (1/4)
0.25 (1/4)
0.75 (3/4)
0.55 (1/2)
1.1 (1.5)
1.1 (1)
2.2 (3)
1.5 (2)
3.0 (3)
2.2 (3)
-
4.0 (5)
Output
kW (HP)
ND
HD
0.37 (1/2)
0.37 (1/2)
0.75 (1)
0.55 (3/4)
1.5 (2)
1.1 (2)
2.2 (3)
1.5 (3)
3.0 (4)
2.2 (3)
4.0 (5)
3.0 (4)
5.5 (7.5)
4.0 (5)
7.5 (10)
5.5 (10)
11.0 (15)
7.5 (10)
15.0 (20)
11.0 (15)
18.5 (25)
15.0 (20)
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Semiconductor Protection Fuse
Time Delay
Fuse
Manufacturer: EATON/Bussmann
Class J, T, and
CC Fuse
Model
Rated Current
A
3
FWH-25A14F
6
FWH-25A14F
10
FWH-60B
15
FWH-80B
25
FWH-100B
30
FWH-125B
-
FWH-150B
Semiconductor Protection Fuse
Time Delay
Fuse
Manufacturer: EATON/Bussmann
Class J, CC,
and T Fuse
Model
Rated Current
A
3
FWH-40B
6
FWH-40B
10
FWH-50B
10
FWH-70B
15
FWH-70B
20
FWH-90B
25
FWH-90B
-
FWH-80B
-
FWH-100B
-
FWH-125B
-
FWH-175B
Rated Current
Input Rated
Current
A
25
25
60
80
100
125
150
Rated Current
Input Rated
Current
A
40
40
50
70
70
90
90
80
100
125
175