Descargar Imprimir esta página

YASKAWA GA500 Instrucciones De Instalación Y Operación página 58

Publicidad

Idiomas disponibles

Idiomas disponibles

Mode
Terminal
l
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2082
-, +1, +2
B1, B2
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-
loop crimp terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of
10 mm
2
(copper wire).
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Recommen
Applicable
ded Gauge
Gauge
2
mm
mm
35
10 - 50
25
10 - 35
50
16 - 70
16
4 - 16
16
10 - 25
Wire
Terminal Screw
Stripping
Length
*1
Size
2
mm
20
M6
20
M6
20
M6
10
M4
-
M6
10 Attachment
Tightening
Torque
Shape
N∙m (in∙lb)
5 - 5.5
(45 - 49)
5 - 5.5
(45 - 49)
5 - 5.5
(45 - 49)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
287

Publicidad

loading