Page 3.0
The regulating set-point can be modified from
Page 3.0.
Depending on the type of regulation chosen on
the previous page, the set-point to be set will be a
head or, in the case of a Constant Curve, a
percentage of the rotation speed.
Page 9.0
On page 9.0 it is possible to choose the parameter
to be displayed on the Home Page:
H: Measured head expressed in metres
Q: Estimated flow rate expressed in m3/h
S: Rotation speed expressed in revs per minute
(rpm)
E: Not present
P: Power distributed expressed in W
h: Operating hours
T: Not present
T1: Not present
Page 10.0
On page 10.0 you can choose the language in
which to display the messages.
Page 11.0
On page 11.0 you can display the alarms log by
pressing the right button.
ENGLISH-
Alarms Log
Page 13.0
11.

FACTORY SETTINGS

Parameter
Regulating mode
Twin operating mode
Pump start control
14
If the system finds any faults it records them
permanently in the alarms log (up to a maximum
of 15 alarms). For each recorded alarm a page
composed of 3 parts is displayed: an
alphanumeric code that identifies the type of fault,
a symbol that illustrates the fault in graphic mode,
and a message in the language selected on Page
10.0, giving a brief description of the fault.
By pressing the right button you can scroll through
all the pages of the log.
2 questions appear at the end of the log:
"Reset Alarms?"
Pressing OK (left button) resets any alarms still
present in the system.
"Delete Alarms Log?"
Pressing OK (left button) deletes the alarms
memorised in the log.
On page 13.0 you can set the system status in ON
or OFF.
If ON is selected the pump is always on.
If OFF is selected the pump is always off.
Value
= Proportional
differential pressure
regulation
= Alternate every 24h
ON
Table 1: Factory settings