Descargar Imprimir esta página

RS Pro RS-3381 Manual De Instrucciones página 5

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

50000 count TRMS heavy Duty AC/DC clamp meter with
dual Type K inputs / English
4-4. AC/DC Voltage Measurements
CAUTION: Do not measure voltages if a motor on the circuit is being switched ON or OFF.
Large voltage surges may occur that can damage the meter.
1. Slide the input shutter to the up position.
2. Rotate the function switch to the V position.
3. Press the MODE button to select AC or DC Voltage.
4. Insert the black test lead banana plug into the negative COM jack.
Insert the red test lead banana plug into the positive V jack.
5. Touch the black test probe tip to the negative side of the circuit.
Touch the red test probe tip to the positive side of the circuit.
6. Read the voltage value in the display.
Frequency
When ACA is selected, the measured frequency can be viewed in the lower display.
6
CAT III
I
MAX
600V
1000A
Non–Contact
Voltage–Delector
AUTO
POWER
OFF
CA P
HOLD
MODE
MAX
RANGE
MIN
PEAK
  
 
AC/DC  TRMS  CLAMP  METER
T2
T1
T ype-K    
V
Hz% CAP
COM
Temp mA µA
V
rspro.com
50000 count TRMS heavy Duty AC/DC clamp meter with
4-5. Resistance Measurements
Note: Remove power from the device under test before making resistance measurements
1. Slide the input shutter to the up position.
2. Set the function switch to the Ω position.
3. Insert the black test lead banana plug into the negative COM jack.
Insert the red test lead banana plug into the positive V jack.
4. Touch the black test probe tip to one side of the device.
Touch the red test probe tip to the other side of the device.
5. Read the resistance value in the display.
Continuity Test
1. Connect as described for resistance measurements.
2. Press the MODE button to select continuity
3. Touch the test probe tips across the circuit or component under test.
4. If the resistance is < 50Ω, a tone will sound.
Diode Test
1. Connect as described for resistance measurements
2. Press the MODE button to select diode test
3. Touch the test probe tips to the diode or semiconductor junction
under test. Note the meter reading.
4. Reverse the test lead polarity by reversing the red and black leads.
Note this reading.
5. The diode or junction can be evaluated as follows:
• If one reading displays a value (typically 0.400V
To 01.800V) and the other reading displays OL, the diode is good.
• If both readings display OL the device is open.
• If both readings are very small or '0', the device is shorted.
rspro.com
dual Type K inputs / English
CAT III
I
MAX
600V
1000A
Non–Contact
Voltage–Delector
AUTO
POWER
OFF
.
CA P
HOLD
MODE
MAX
RANGE
MIN
PEAK
  
 
AC/DC  TRMS  CLAMP  METER
T1
T ype-K    
T2
V
Hz% CAP
.
COM
Temp mA µA
7

Publicidad

loading

Este manual también es adecuado para:

200-3702