SPECIFICATIONS
POWER SUPPLY
................................................................................
MAX POWER CONSUMPTION
TEMPERATURE ADJUSTMENT RANGE
REGULATION RESOLUTION
ROOM TEMPERATURE DISPLAY
DIFFERENTIAL REGULATION VALUE
ON-BOARD ROOM TEMPERATURE SENSOR
WATER TEMPERATURE PROBE (NOT SUPPLIED)
OUTPUTS
................................................................................................
CONTACT RATING
..............................................................................
DEGREE OF PROTECTION
INSULATION CLASS
...........................................................................
DEGREE OF
POLLUTION....................................................................
SOFTWARE CLASS
.............................................................................
THERMAL GRADIENT
MAXIMUM OPERATING TEMPERATURE
HUMIDITY LIMITS
..............................................................................
STORAGE TEMPERATURE
SWITCHING
..........................................................................................
ASSEMBLY
.............................................................................................
........................................................
..........................................
...........................................................
.....................................................
...........................................
...........................
.................................................................
.....................................................................
.......................................
................................................................
230V~/50Hz (+10% -15%)
3VA
5°C÷35°C
0,1°C
0÷40°C (resolution 0,1°C)
SETTABLE (0,5K factory setting)
NTC 100K @25°C ±1%
NTC 2K @25°C with double insulation
......................
4 Relays (3 motor speeds + 1 solenoid valve)
3(1A) – 250Vac
IP 20 (with installed product)
2
A
1K/15min.
50°C
20% .. 80% RH (non-condensing)
0÷60°C
SUMMER/WINTER (heating/air conditioning)
in standard, 3-module flush-mounting box (DIN503)