4.6.2.1
Mains connection PTF 6x.xxx
Fig. 10: Mains connection PTF 6x.xxx
1
Mains terminal strip
2
Strain relief (cable tie)
NOTE
Protective conductors in the mains connection cable are not regarded as potential equalization conductors.
Prerequisite
DANGER – Danger to life due to electric shock. Make sure that the unit is voltage-free.
•
All general requirements for safe and reliable operation are fulfilled.
Procedure
1.
Connect to mains as shown in the circuit diagram (terminal designation).
2.
Open the cage clamp terminal of the mains terminal strip with the flat screwdriver and connect the cables on the mains
terminal strip.
ATTENTION – Damage to the cage clamp terminal.
Firmly insert the screwdriver into the cage clamp terminal. Never turn it, otherwise the cage clamp terminal will be
damaged.
2.
Secure the power cable to the strain relief with a cable tie.
3.
Before switching on, make sure that the mains voltage matches the data on the type plate.
Electrical connection of the top filterfan is completed.
Operating Manual | Top Filterfans / Top Exhaust Filter | – 230 / 115 V | 086150000
3
Cable 1.5 to 2.5 mm², stripping length 8 to 9 mm
4
Screwdriver (flat, max. 3.5 mm)
28/40