Descargar Imprimir esta página

Aprimatic RSK24 Instrucciones Para La Instalación, Uso Y Mantenimiento página 21

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

4.2
RESET
If you want to return all the programmed parameters to their default settings, you should RESET the unit as follows:
Switch off the power supply.
Press and hold down the BLUE button and at the same time switch the power supply back on again.
will appear fl ashing on the display. This indicates that you must repeat the self-teach cycle.
Press the YELLOW and BLUE buttons together for several seconds (for details see section 3.1.1).
5.1
OPERATING MODES
During the operating cycle the system handles the following signals:
STOP pulse and START pulse.
Closing safety photocell.
Opening safety device (photocell, safety edge ...).
Detection of any obstacle on the opening and closing strokes.
Operation of the automation functions in response to these
signals depends on the operating mode selected.
The system operates in the automatic mode depending on the
default settings. For instructions on changing the operating
mode, see sect. 7.1.
The next section describes the operating modes and the
signal responses for each operating mode.
AUTOMATIC MODE (default mode) (0)
Starting with the gate closed, the complete operating cycle
is as follows:
The START pulse is given.
After 3 seconds, wing 2 starts to open.
When both wings are opened as far as the mechanical stop,
the gate will stay open for the programmed pause time.
Next, wing 2 will start to close.
After the preset delay time, wing 1 will start to close.
During the opening cycle, START pulses will be ignored and
signals from closing photocells will also be ignored.
During the closing cycle, any START pulses or signals from
closing photocells will trigger reopening of the wings.
During the pause time with the gate open, the closing
photocells will keep the gate stopped and open until they
are uncovered.
4-STEP MODE (1)
Starting with the gate closed, the complete operating
cycle is the same as that for the automatic mode.
If a START pulse is not given within the fi rst 3 seconds
of the opening pause
automatically.
If a START pulse is given within the fi rst 3 seconds of
the pause time
the gate will stay locked in the open
position; to close the gate in this case you must give the START pulse again.
SUPER AUTOMATIC MODE (2)
Starting with the gate closed, the complete operating cycle is the same as that for the automatic mode.
The START pulse in any stage of a movement
to close the gate using the control.
SEMIAUTOMATIC MODE WITH STOP (3)
Starting with the gates closed:
START pulse
the wings open and the gate stays stopped in the open position.
The START pulse during opening stops the wings.
The START pulse during closing
STEP-BY-STEP MODE (4)
Starting with the gates closed:
START pulse
the wings open and the gate stays stopped in the open position.
The START pulse during opening stops the wings.
The START pulse during closing stops the wings.
Wing 1 starts to open.
the gate will start to close
reverses the direction of movement of the gate; it will be possible
reopens the wings.
Automatic logic:
1
gate closed
2
gate open
1
Another START pulse will close the gate.
Another START pulse will close the wings.
Another START pulse will close the gate.
Another START pulse will close the wings.
Another START pulse will reopen the wings.
- 21 -
Reset - Functioning logic
The letter S
START pulse
2
3"
3
gate opening
pause time
4
gate closing
1
2
Fig. 8

Publicidad

loading