Descargar Imprimir esta página

Mitsubishi Electric CITY MULTI TPKFYP-BM142 Serie Manual De Instalación página 7

Publicidad

Idiomas disponibles

Idiomas disponibles

5. Electrical work
<Example of "F2" calculation>
• Condition TPEFYP∙MS × 4 + TPEFYP∙MA × 1, C = 8 (refer to right sample chart)
F2 = 19.8 × 4/8 + 38 × 1/8
= 14.65
→ 16 A breaker (Tripping current = 8 × 16 A at 0.01 s)
*3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type1) + V2 × (Quantity of Type2) + V2 × (Quantity of Type3) + V2 × (Quantity of Others)
+ V3 × (Wire length[km])
G1
Current sensitivity
30 or less
30 mA 0.1sec or less
100 or less
100 mA 0.1sec or less
2
Wire thickness (mm
/AWG)
2.1/14
3.3/12
5.3/10
M1 M2
M1 M2
S
T
B
3
T
B
5
M1 M2
M1 M2
S
TB3
TB5
Pair No.
M1 M2
M
0
TB3
TB5
Pair No.
0
Fig. 5-4
V3
48
56
66
M1 M2
S
T
B
5
CN3A
CN3A
M1 M2
S
TB5
Pair No.
1
M
2
S
M1 M2
S
0
TB5
1
2
1
5.3. Types of control cables
1. Wiring transmission cables
Types of transmission cable
Cable diameter
Length
2. M-NET Remote control cables
Types of remote control cable
Cable diameter
Length
3. MA Remote control cables
Types of remote control cable
Cable diameter
Length
5.4. Connecting remote controller, indoor and
outdoor transmission cables (Fig. 5-4)
• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire) The "S"
on indoor unit TB5 is a shielding wire connection. For specifications about the
connecting cables, refer to the outdoor unit installation manual.
Note:
As for TPKFYP∙BM142 series, TB5 has two terminals and does not have S
terminal. The earths of shielding wires are crimping-connected. Insulate the
connected parts with insulating tapes and so on.
• Install a remote controller following the manual supplied with the remote
controller.
• Connect the remote controller's transmission cable within 10 m, 33 ft using a
0.75 mm
(AWG22) core cable. If the distance is more than 10 m, 33 ft, use a
2
1.25 mm
(AWG16) junction cable.
2
1 MA Remote controller
• Connect the connector for a MA remote controller. (Non-polarized 2-wire)
• DC 9 to 13 V between 1 and 2 (MA remote controller)
2 M-NET Remote controller
• Connect the "M1" and "M2" on indoor unit TB5 to a M-NET remote controller.
(Non-polarized 2-wire)
• DC 24 to 30 V between M1 and M2 (M-NET remote controller)
3 Wireless remote controller (When installing wireless signal receiver)
• Connect the wire of wireless signal receiver (9-pole cable) to CN90 of indoor
controller board.
• When more than two units are run under group control using wireless remote
controller, connect connector b each with the same number.
• To change Pair No. setting, refer to installation manual attached to wireless
remote controller. (In the default setting of indoor unit and wireless remote
2
controller, Pair No. is 0.)
Terminal block for indoor transmission cable
A
Terminal block for outdoor transmission cable (M1(A), M2(B),
B
Remote controller
C
Wireless signal receiver
D
Wireless remote controller
E
Sample chart
6000
600
SAMPLE
60
10
1
0.1
0.01
1
2
3
4
6
Rated Tripping current (x)
Shielding wire CVVS or CPEVS
More than 1.25 mm
(AWG16)
2
Less than 200 m, 219 yard
Shielding wire MVVS
More than 0.5 (AWG20) to 1.25 mm
2
Add any portion in excess of 10 m, 33 ft to
within the longest allowable transmission cable
length 200 m, 219 yard.
2-core cable (unshielded)
0.3 (AWG22) to 1.25 mm
(AWG16)
2
Less than 200 m, 219 yard
(S))
8
10
20
C
(AWG16)
7

Publicidad

loading