Descargar Imprimir esta página

Victron energy BLUE POWER MultiPlus 12 5000 200-50 Manual página 24

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

5.5.2 Step 2: Other settings
The remaining settings are not relevant (na) for slaves.
Some of the remaining settings are not relevant for followers (L2, L3). These settings are imposed on the whole system by the leader
L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
Absorption
ds8-ds7
voltage
14.1
off
off
28.2
56.4
14.4
off
on
28.8
57.6
14.7
on
off
29.4
58.8
15.0
on
on
30.0
60.0
ds6: absorption time 8 or 4 hours (na for L2, L3)
ds5: adaptive charging characteristic (na for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency (na for L2, L3)
(the wide input frequency range (45-55Hz) is 'on' by default)
Step 2: Exemplary settings for stand-alone mode
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to 'off' and do
not reflect the actual settings in the microprocessor.).
DS-8 Ch. voltage
off
DS-7 Ch. voltage
on
DS-6 Absorpt. time
on
DS-5 Adaptive ch.
on
DS-4 Dyn. Curr. limit
off
DS-3 UPS function:
on
DS-2 Voltage
on
DS-1 Frequency
on
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 230V
1 Frequency: 50Hz
To store the settings after the required values have been set: press the 'Down' button for 2 seconds (lower button to the right of the DIP
switches). The temperature and low-battery LED's will flash to indicate acceptance of the settings.
You can then leave the DIP switches in the selected positions, so that the 'other settings' can always be recovered.
20
Float
Storage
oltage
voltage
13.8
13.2
Gel Victron Long Life (OPzV)
27.6
26.4
Gel Exide A600 (OPzV)
55.2
52.8
Gel MK battery
Gel Victron Deep Discharge
13.8
13.2
Gel Exide A200
27.6
26.4
AGM Victron Deep Discharge
55.2
52.8
Stationary tubular plate (OPzS)
AGM Victron Deep Discharge
13.8
13.2
Tubular plate traction batteries in
27.6
26.4
semi-float mode
55.2
52.8
AGM spiral cell
13.8
13.2
Tubular plate traction batteries in
27.6
26.4
cyclic mode
55.2
52.8
DS-8
off
DS-8
DS-7
off
DS-7
DS-6
on
DS-6
DS-5
on
DS-5
DS-4
off
DS-4
DS-3
off
DS-3
DS-2
on
DS-2
DS-1
on
DS-1
Step 2
Step 2
Example 2:
Example 3:
8, 7 OPzV 14,1V
8, 7 AGM 14,7V
6 Abs. time: 8 h
6 Abs. time: 8 h
5 Adaptive ch.: on
5 Adaptive ch: on
4 Dyn. Curr. limit: off
4 Dyn. Curr. limit: on
3 UPS function: off
3 UPS function: off
2 Voltage: 230V
2 Voltage: 240V
1 Frequency: 50Hz
1 Frequency: 50Hz
Suitable for
on = 8 hours
off = 4 hours
on = active
off = inactive
on = active
off = inactive
on = active
off = inactive
on = 230V
off = 240V
on = 50Hz
off = 60Hz
on
DS-8
on
off
DS-7
on
on
DS-6
off
on
DS-5
off
on
DS-4
off
off
DS-3
on
off
DS-2
off
on
DS-1
off
Step 2
Example 4:
8, 7 Tub.-plate 15V
6 Abs. time: 4 h
5 Fixed abs. time
4 Dyn. Curr. limit: off
3 UPS function: on
2 Voltage: 240V
1 Frequency: 60Hz
(inactive = fixed absorption time)

Publicidad

loading