Regulation and control
Description
RE
Probe to be displayed 0=All probes (sequential)
C21
1=Probe 1 (Chamber) 2=Probe 2 (Evaporator)
C22
Stop fans and compressor on opening door 0=No 1=Yes
C23
Start-up delay for fans and compressor with door open
C27
Probe 3 calibration (Offset)
EP
Exit to level 1
Defrost
Description
d0
Defrost frequency (Time between 2 starts)
DEF
d1
Maximum defrost duration (0=defrost deactivated)
Type of message during the defrost:
d2
0=Displays the real temperature; 1=Displays the temperature at the start of the
defrost; 2=Displays the dEF message
Maximum duration of the message
d3
(Time added at the end of the defrost process)
d4
Final defrost temperature (by probe) (If I00 ¹ 1)
Defrost on connecting the unit:
d5
d6
Delay of the defrost start on connecting the unit
Type of defrost:
†
d7
Count of time between defrost periods:
d8
0=Total real time 1 =Sum of compressor connected time
d9
Drip time when completing defrost (Shutdown of compressor and fans)
EP
Exit to level 1
Evaporator fans
Description
F0
Shutdown temperature of fans
fAN
F1
Probe 2 differential if fans are shut down
F2
Shut down fans when the compressor shuts down
F3
Status of the fans during the defrost 0=Shut down; 1=Running
Delay of start-up after defrost (If F3=0)
F4
It will only actuate if it is higher than d9
EP
Exit to level 1
* According to wizard.
†
It can only be modified using the configuration wizard (InI).
3=Probe 3 (According to I20)
0=NO First defrost according to d0;
1=YES, First defrost according to d6
0=Resistors;
1=Air/fans
2=Hot gas;
3=Reversal of cycle
0=No 1=Yes
15
1652H311 Ed.11
Values Min.
Def. Max.
0
1
0
0
Min.
0
0
999
ºC/ºF
-20.0
0.0
20.0
Values Min.
Def. Max.
H.
0
6
96
*
Min.
0
255
0
2
Min.
0
5
255
ºC/ºF
-50
8.0
50
0
0
Min.
0
0
255
*
0
0
0
Min.
0
1
255
Values Min.
Def. Max.
ºC/ºF
-50
45
50
ºC/ºF
0.1
2.0
20.0
0
0
0
0
Min.
0
2
99
3
1
2
1
3
1
1
1