Descargar Imprimir esta página

Mitsubishi Electric TRANE TPEFYP006MS140C Manual De Instalación página 11

Ocultar thumbs Ver también para TRANE TPEFYP006MS140C:

Publicidad

Idiomas disponibles

Idiomas disponibles

<Table 1>
System ������
Transmission cable length
Facility example
Residence or independent
(for noise judgment)
store without noise
VCTF, VCTFK, CVV, CVS,
Types of transmission
VVR, VVF, VCT or shielding
cables
wire CVVS or CPEVS
Length
2. Remote controller cables
Types of cables
Sheathed 2-core cable (unshielded) CVV
Cable diameter
0.3 to 1.25 mm
Length
Less than 200 m [656 ft]
9.1. Power supply wiring
Power supply cords of appliances shall not be lighter than design 245 IEC 57, 227 IEC 57, 245 IEC 53 or 227 IEC 53.
A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.
[Fig. 9.1.1] (P.4)
Ground-fault interrupter
A
Local switch/Wiring breaker
B
Indoor unit
C
Pull box
D
Minimum wire thickness (mm
Total operating current of
the Indoor unit
Main cable
F0 = 15 or less *
2.1/14
2
F0 = 20 or less *
3.3/12
2
F0 = 30 or less *
5.3/10
2
Apply to IEC61000-3-3 about Max. Permissive System Impedance.
*1 The Ground-fault interrupter should support Inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + {V1 × (Quantity of Others)/C}
Indoor unit
Type1
TPEFYP***MS140C
Type2
TPEFYP***MA143A, TPVFYP***AM140(1)A
Type3
TPEFYP***MH140A
Type4
TPCFYP***KM140B
TPKFYP***HM142A, TPKFYP***KM142A,
Type5
TPMFYP***BM140E
Type6
TPLFYP***EM140(1)A, TPLFYP***FM140A
Others
Other indoor unit
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
* Condition TPEFYP***MS140C × 4 + TPEFYP***MA143A × 1, C = 8 (refer to right sample chart)
F2 = 18.6 × 4/8 + 38 × 1/8
= 14.05
➞ 16 A breaker (Tripping current = 8 × 16 A at 0.01s)
*3 Current sensitivity is calculated using the following formula.
G1 = (V2 × Quantity of Type1) + (V2 × Quantity of Type2) + (V2 × Quantity of Type3) + (V2 × Quantity of Others) + (V3 × Wire length [km])
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too large capacity may cause a risk of malfunction
or fire.
For a single-refrigerant system
Less than 120 m [394 ft]
Building, clinic, hospital or communications
station without noise supposedly generated
from inverter equipment, private power
generator, high-frequency medical equipment,
radio-used communications equipment and
so on
Less than 120 m [394 ft]
MA remote controller
[AWG22 to 16]
2
/AWG)
2
Ground-fault interrupter *
Branch
Ground
2.1/14
2.1/14
15A current sensitivity *
3.3/12
3.3/12
20A current sensitivity *
5.3/10
5.3/10
30A current sensitivity *
Wire thickness
1.5 mm
2
2.5 mm
2
4.0 mm
2
More than 120 m [394 ft]
Shielding wire CVVS or CPEVS
M-NET remote controller
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm
[AWG22 to 16]
2
Add any portion in excess of 10 m [32 ft] to within the longest allowable transmission
cable length 200 m [656 ft] (Shielding portion is more than 1.25 mm
Local switch (A)
1
Capacity
Fuse
15
15
3
20
20
3
30
30
3
V1
V2
18.6
2.4
38
1.6
13.8
4.8
19.8
2.4
9.9
2.4
17.1
2.4
0
0
V3
48
56
66
For a multi-refrigerant system
Regardless of length
All facilities
Less than 200 m [656 ft]
[AWG16])
2
Breaker for wiring (A)
(Non-fuse breaker)
15
20
30
6000
600
SAMPLE
60
10
1
0.1
0.01
1
2
3
4
6
8
10
C
Rated Tripping current (x)
Sample chart
20
11

Publicidad

loading