Descargar Imprimir esta página

Lamborghini Caloreclima AXE 3 D UNIT 32 R Instrucciones De Uso, Instalación Y Mantenimiento página 16

Ocultar thumbs Ver también para AXE 3 D UNIT 32 R:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

5. TECHNICAL DATA AND CHARACTERISTICS
5.1 Dimensions, connections and main components
32
295
fig. 19 - Dimensions, connections and main components
36
10
11
14
11
226
A4
Flue - Ø 120 ÷ 130
10
System delivery 3/4"
11
System return 1"
16
EN
500
700
56
246
278
32
295
fig. 20
a4
10
275
222
52
fig. 21
cod. 3540Z340 - 03/2011 (Rev. 00)
AXE 3 D UNIT 32 R
32
Heating circulating pump
36
Automatic air vent
56
Expansion tank
246
Pressure transducer
275
Heating system drain cock
278
Double sensor (Heating + Safety)
295
Burner
5.2 Technical data table
Data
Number of elements
Max. heating capacity
Min. heating capacity
Max. heat output in heating
Min. heat output in heating
Efficiency Pmax (80-60°C)
Efficiency 30%
Efficiency class Directive 92/42 EEC
Max. working pressure in heating
Min. working pressure in heating
Max. heating temperature
Heating water content
Heating expansion tank capacity
Heating expansion tank prefilling pressure
Protection rating
Power supply voltage
Electrical power input
Empty weight
Combustion chamber length
Combustion chamber diameter
Pressure loss on fumes side
5.3 Pressure loss
Circulating pump head / pressure loss
6
3
5
2
4
3
1
2
1
0
0
500
fig. 22 - Circulating pump head / pressure loss
Unit
AXE 3 D UNIT 32 R
no.
3
kW
34.3
kW
16.9
kW
32
kW
16
%
93.3
%
94.3
bar
6
bar
0.8
°C
95
litres
12.5
litres
8
bar
1
IP
X0D
V/Hz
230/50
W
320
kg
166
mm
365
mm
326
mbar
0.16
1.000
1.500
Q [l/h]
(Q)
(Q)
(P)
(P)
(PMS)
(tmax)
A
2.000

Publicidad

loading