6. Enter the command"^S006SOP31" to set the UPS to 31 model, UPS will
return "^D006ACK" when it accepts. If you want to set the UPS to 33 model,
the command is "^S006SOP33".
Note: this parameter setting is not effected immediately. The setting will be saved
only when UPS shutdown normally and with battery connection.
7.
After the UPS is shut down normally, the output terminals need to be shorted.
31 Schematic diagram of the connection of short circuit sheet copper
33 Schematic diagram of the connection of short circuit sheet copper
ON-LINE 3P/3P