DIP-SWITCH SETTING
Turn off the power to the unit. This
operation should be carried out in the
installation phase, by suitably trained and
qualified personnel only.
The dip-switches are on the electronic board.
**Warning: if the thermostats are inserted
DIP
DIP 1
DIP 2
DIP 3
DIP 4
DIP 5
DIP 6
DIP 7
DIP 8
38
in systems with Centralised Control or
Supervisor (e.g. VMF-E5), it is necessary to
set: Dip1=ON and Dip2=OFF. The setting
takes priority over the presence of the
valve and the position of the probe.
Position
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
Function
With shut-off valve
No shut-off valve
Water probe upstream of the valve
Water probe downstream of the valve
Continuous ventilation
Thermostat-controlled ventilation
Reduced band enabling
Normal band enabling
4-pipe fan coil
2-pipe fan coil
Supplementary heater present
Supplementary heater not present
Dead band 2°C
Dead band 5°C
Management of electric heater in replacement mode (2t + 2f )
Management of the electric heater in replacement mode