10. Reference Materials
Model SU100KMBPKX
REAR VIEW
MECHANICAL LUG CONNECTIONS
INPUT
OUTPUT
NEUTRAL
GROUND
GROUND
TO UPS AC INPUT
Notes:
1. "SW1" UPS INPUT SWITCH.
2. "SW2" MAINTENANCE BYPASS SWITCH.
3. "SW3" MAINTENANCE ISOLATION SWITCH.
4. MODELS SU120KMBPK, SU160KMBPKX, SU180KMBPKX, SU210KMBPKX – "SW2" AND "SW3" SWITCHES ARE CONNECTED WITH (2) 1/0 WIRES PER
PHASE. MODEL SU100KMBPKX – "SW2" AND "SW3" SWITCHES ARE CONNECTED WITH (1) 1/0 WIRE PER PHASE.
5. MODELS SU120KMBPK, SU160KMBPKX, SU180KMBPKX, SU210KMBPKX – "SW1" AND "SW3" SWITCH LUGS ACCEPT (2) #6 – 250 MCM WIRE PER
PHASE. MODEL SU100KMBPKX – "SW1" AND "SW3" SWITCH LUGS ACCEPT (1) #6 – 350 MCM WIRE PER PHASE.
6. GROUND LUG ACCEPTS (4) #6 – 350 MCM WIRE.
7. MECHANICAL LUGS USED FOR THE UTILITY INPUT AND THE OUTPUT TO LOAD HAVE THE SAME WIRE RANGE AS THE SWITCHES.
8. THIS DRAWING IS TO BE USED FOR ELECTRICAL PURPOSES ONLY AND DOES NOT REPRESENT THE ACTUAL MECHANICAL LAYOUT OF THE EQUIPMENT.
TOP VIEW
FRONT VIEW
WIRE RANGE & TORQUE VALUE SUMMARY
WIRE RANGE
#6 - 250 MCM
#6 - 250 MCM
#2 - 600 MCM
#6 - 350 MCM
#22 - #10 AWG
UTILITY INPUT
8
SIDE VIEW
375 in-lbs. (42.4 Nm)
375 in-lbs. (42.4 Nm)
500 in-lbs. (56.5 Nm)
375 in-lbs. (42.4 Nm)
16 in-lbs. (1.8 Nm)
OUTPUT TO LOAD
ISOMETRIC VIEW
TORQUE VALUE
TO UPS AC OUTPUT