Descargar Imprimir esta página

Hitachi PSC-A64S Manual De Instalación Y Funcionamiento página 13

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 37
4.1. GROUP SETTING PROCEDURE
- The group setting consists of the master unit setting and the slave unit setting. The indoor unit,
which is connected directly to the remote control switch, is set as the master unit, and the indoor
unit connected with the transmission line is set as the slave unit.
- Without the remote control switch, the control by the remote control switch group is not
available. Therefore, in this case, one indoor unit is set as one group. (Only the master unit is
set without the slave unit).
- When setting the remote control switch group without transmission line between indoor units,
the indoor unit connected with the remote control switch shall be set as master unit.
- When using the remote control switch (PC-AR(T)), the half-sized remote control switch
(PC-ARH) or receiver kit (PC-ALH∗), after the setting of master unit, the central station
automatically set the slave unit.
- Check for the setting state by the slave unit setting mode.
4.1.1. SYSTEM OF LESS THAN 16 INDOOR UNITS CONNECTED, REFRIGERANT SYSTEM
ADRESS AND INDOOR UNIT ADRESS.
The group is automatically set as zone Nº 1 by the indoor unit address regardless of the refrigerant
cycle address. Set the indoor unit address without duplication of address.
Central
Station
Setting of
0
Indoor Unit RSW
1
Group Number
- When using the remote control switch (PC-AR(T)) or the half-sized remote control switch
(PC-ARH) and the receiver kit (PC-ALH∗), the indoor units are automatically recognized as
the slave unit of the indoor unit 2 and set to the group 3. (The setting of the slave unit is not
required. However, the contents of the setting should be checked.)
- When using other controllers than the described above, the indoor unit can not be
recognized as the slave unit automatically, and set as the master unit of group 5. In this case
change the setting to the slave unit of the group 3 according to the above "Group Setting
Procedure".
GROUP SETTING
1
2
3
*
2
3
The setting "0" to "15" or
"0" to "F" of indoor unit
RSW is corresponding to
the group Nº. "1" to "16" of
central station.
(The setting can be
changed by the procedure
of "4.3. System of more
4
than 17 indoor units
connected")
5
7

Publicidad

loading