Pre-Installation
1. Proper electrical supply (208, 220 or 240 Volt): See rating label on Steam Generator and Chart on page 14. Determine proper size of wire, voltage,
amperage, and phase for the Steam Generator. 90°C copper wire is required for generator connection.
2. In-line fuse/circuit breaker required: Fuse/circuit breaker to be installed must be sized in accordance with chart on back page. Do NOT install a GFI
(Ground Fault Interrupter) to this equipment (per article 210-8 in the National Electric Code).
3. Route power supply cable to the location where the Steam Generator will be installed (before walls are closed).
Electrical Rough-in
1. Route appropriate power cable to the location the steam generator will be installed. If receptacle is desired, mount the box for the receptacle near
the location of the steam generator.
NOTE: The plug and receptacle require a rating of no less than 250v and proper amperage. Refer to chart on page 14 for amperage rating. After the
walls are complete, the steam generator and control can be wired.
Steam Generator Electrical Installation
1. Remove the two screws holding the electrical access cover and remove cover.
2. Locate the supply line knockout. Mount proper strain relief into knockout hole.
3. Strip back power cable's outer insulation jacket eight inches and insert into steam generator. Strip back insulation ½" from the three (3) incoming
wires (two power and one ground).
4. Insert ground wire into grounding lug located on the right side of the electrical compartment and secure.
5. Locate the terminal/fuse block in the upper portion of the electrical compartment. Insert power wires into the power lugs on the front of the terminal/
fuse block and secure.
Optional Auto Drain Valve Connection
1. Open knockout for auto drain valve conduit connection.
2. Route flexible conduit from valve to knockout and secure.
3. Connect two wires from valve to the auto drain connection J11 on the printed circuit board (see Figure 2).
Ganging Multiple Steam Generators
IMPORTANT: When ganging 2 to 4 steam generators together an additional steam head and control cable must be purchased for each additional gen-
erator.
1. Locate the control cable knockout at top of steam generator. Mount proper strain relief into knockout hole (see Figure 3).
2. Route control cable from any one of the 3 modular jacks located on the circuit board to the steam generator to be ganged (see Figure 3).
3. Set DIP switches on each additional steam generator's main PCB as shown in the gangable generators chart (see Figure 3).
Internal Electrical Connection/Conexión Eléctrica Interna/Connexion électrique interne
Figure 2
Alternate knockouts for control cables
Hoyos ciegos para el cableado de control
Autres entrées défonçables pour les câbles de commande
Water level probe
Sonda para medir el nivel del agua
Sonde de niveau d'eau
DIP switches for ganging generators
Interruptores DIP para generadores agrupados
Commutateurs DIP pour générateurs groupés
Troubleshooting LED's
Solución de averías del LED
Voyants de dépannage à DEL
Optional auto drain connection
Conexión de drenaje automático
opcional
Connexion du dispositif de
vidange automatique facultatif
All power to the Steam Generator must be turned off during installation.
Be sure the ground wire does not come in contact with a live electrical
part.
Test button
Botón de prueba
Bouton de test
208/220/240V incoming power
connections
Conexiones eléctricas de
entrada de 208/220/240 V
Connexions pour alimentation
de 208/220/240 V
Knockout for electrical supply line
Agujero ciego para línea de suministro eléctrico
Entrée défonçable pour le câble d'alimentation électrique
WARNING
!
WARNING
!
Plug
Enchufe
Fiche
Modular Jacks (Plug control cable into any connector)
Tomas modulares (enchufe el cableado de control en un conector.
Prises modulaires (branchez le câble de commande dans l'une des prises)
PC Board
Tabla del circuito
Carte de circuits
imprimés
Ground
Tierra
Terre
10
Knockouts for control cables
Hoyos ciegos para el cableado de
control
Entrées défonçables pour les câbles de
commande
Water inlet 3/8" compression fitting
Accesorio de compresión de 3/8" del
agua de entrada
Raccord à compression de l'entrée d'eau
de 3/8 po
Safety relief valve
Válvula de seguridad
Soupape de sûreté
3/4" Steam outlet
Salida de vapor 3/4"
Sortie de vapeur de 3/4 po
Optional auto drain shown installed
Drenaje automático opcional se muestra
instalado
Dispositif de vidange automatique
facultatif installé