Descargar Imprimir esta página

Ferroli BLUEHELIX TECH RRT 24 H Instrucciones De Uso, Instalación Y Mantenimiento página 191

Ocultar thumbs Ver también para BLUEHELIX TECH RRT 24 H:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

BLUEHELIX TECH RRT 24 H
Circulating pump
Before carrying out the following instructions it is advisable to protect the room and the boiler's electrical box
A
against accidental water spillage.
1
2
fig. 38
Disconnect the power supply and close the gas cock ahead of the valve.
Electrically disconnect the circulating pump, releasing the connections by raising the detail "1" in fig. 38.
Drain the water in the boiler (see "System draining" on page 162).
Unscrew and remove the circulating pump motor assembly (fig. 40)
Replacing the main exchanger
Before carrying out the following instructions it is advisable to protect the room and the boiler's electrical box
A
against accidental water spillage.
3
1
Disconnect the power supply and close the gas cock ahead of the valve
Disconnect the fume sensor connector
Disconnect the fan connector
Disconnect the connector of the ignition electrode connected to the board.
EN
fig. 39
4
1
2
1
2
fig. 41- Main exchanger
cod. 3541C662 - Rev. 00 - 09/2020
3
1
fig. 40
5
5
6
5
5
191

Publicidad

loading