3. REFRIGERANT PIPING
3.1. PIPING CONNECTION
Access to the refrigerant Pipes connections by removing the
Fan cover from the unit.
The location of refrigerant pipes connection is the following:
(Detail of A)
Gas Piping
Liquid Piping
Liquid Piping
Gas Piping
REFRIGERANT PIPING
Size of piping connection
Model RPIM
Pipe size
Gas Piping
Ø 12.7 (1/2")
Liquid Piping
Ø 6.35 (1/4")
Flare Pipe Dimensions
Nominal
d
A
Diameters
1/4"
6.35
3/8"
9.53
1/2"
12.7
5/8"
15.88
Flare Nut Dimensions
Nominal
Outer
Diameters
Diameters
1/4"
6.35
3/8"
9.53
1/2"
12.70
5/8"
15.88
Thickness of Copper Pipes
Nominal
Outer Diameters
Diameters
1/4"
6.35
3/8"
9.53
1/2"
12.7
5/8"
15.88
3
5
(mm)
(mm)
+0/-0.4
9.1
13.2
16.6
19.7
(mm)
B
17
22
26
29
(mm)
Thickness
0.80
0.80
0.80
1.00