4.25. The installation shown below is the most common. Please bear in mind that if the gas flue pipe located on
the outside of the dwelling is in an area where people pass by, insulated tube must be used.
Windbreak.
Stainless steel hose clamp.
T of 90° with outlet.
Insulator.
Wooden ground.
Non flammable floor protection.
Distance equal to or less than 2 metres.
4.26. If for aesthetic, safety or municipal regulations we cannot install the stove as described above, we can always
install the pipe on the inside of the dwelling, paying special attention to the areas where the pipe touches
structures, and the minimum vertical and maximum horizontal lengths.
Windbreak.
Stainless steel hose clamp.
T of 90° with outlet.
Insulator.
Wooden ground.
Non flammable floor protection.
Elbow of 90°.
Distance equal to or over 2 metres.
1(
MAXIMUM 1 metre.
4.27. When fitting stoves in brickwork chimneys a perfect seal between the flexible and the rigid pipe must be
achieved. Similarly, the insulation to be placed at the contact areas between the pipe and possibly
inflammable zones must be taken into account. The tube end may be left inside the chimney itself, taking
into account its opening.
Once installation is complete, we must seal the chimney from the inside of the house.
33
Drawing 6
Drawing 7