Pre-Installation
• Proper electrical supply (240 Volt): See rating label on Steam Generator and Chart on page 13. Determine proper size of wire, voltage, amperage,
and phase for the Steam Generator. 90°C copper wire is required for generator connection.
• In-line fuse/circuit breaker required: Fuse/circuit breaker to be installed must be sized in accordance with chart on back page. Do NOT install a GFI
(Ground Fault Interrupter) to this equipment (per article 210-8 in the National Electric Code).
• Route power supply cable to the location where the Steam Generator will be installed (before walls are closed).
Electrical Rough-in
• Route appropriate power cable to the location the Steam Generator will be installed. If receptacle is desired, mount the box for the receptacle near
the location of the Steam Generator.
NOTE: The plug and receptacle require a rating of no less than 250V and proper amperage. Refer to specification chart for amperage rating. After the
walls are complete, the Steam Generator and Control can be wired.
Steam Generator Electrical Installation
All power to the Steam Generator must be turned off.
• Remove the two screws holding the electrical access cover and remove cover.
• Locate the supply line knockout. Mount proper strain relief into knockout hole.
• Strip back power cable's outer insulation jacket eight inches and insert into Steam Generator. Strip back insulation ½" from the three (3) incoming
wires (two power and one ground).
• Insert ground wire into grounding lug located on the right side of the electrical compartment and secure.
Be sure the ground wire does not come in contact with a live electrical
part.
• Locate the terminal/fuse block in the upper portion of the electrical compartment. Insert power wires into the power lugs on the front of the terminal/
fuse block and secure.
Optional Auto Drain Valve Connection
• Open knockout for Auto Drain Valve conduit connection.
• Route flexible conduit from valve to knockout and secure.
• Connect two wires from valve to the auto drain connection J11 on the printed circuit board (see Figure 2A).
Internal Electrical Connections 5P-EST04, 5P-EST06, 5P-EST07, 5P-EST10
Conexiones eléctricas internas 5P-EST04, 5P-EST06, 5P-EST07, 5P-EST10
Connexions électriques internes – 5P-EST04, 5P-EST06, 5P-EST07 et 5P-EST10
Figure 2A
Figura 2A
Figure 2A
Knockouts for control cables
Troqueles para cables de
Entrées défonçables pour
les câbles de commande
WARNING
!
CAUTION
!
Multi-conductor control cable
control
Cable de control multi-
conductor
Câble de commande multicon-
ducteur
Plug
Enchufe
Fiche
Modular Jacks (Plug control cable into any connector)
Conectores modulares (enchufe el cable de control en cualquier
conector)
Prises modulaires (branchez le câble de commande dans l'une des
prises)
Ground connection
Conexión a tierra
Connexion de la mise à la terre
L1 & L2 power connections
Conexiones de alimentación
L1 y L2
Connexions d'alimentation
L1 et L2
Optional auto drain connection
Conexión de drenaje automático
opcional
Connexion du dispositif de vidange
automatique facultatif
10
240v incoming power
connections
Conexiones de entrada
de alimentación eléctrica
de 240v
Câble d'alimentation 240 V
3/4" Steam outlet
Salida de vapor 3/4"
Sortie de vapeur 3/4 po
Safety relief valve
Válvula de seguridad
Soupape de sûreté
1/2" Outlet when not equipped with
optional auto drain this line should
remain capped.
Salida de 1/2" cuando no está
equipada con drenaje automático
opcional, esta línea debe permanecer
tapada.
Sortie 1/2 po. Si le générateur n'est
pas équipé du dispositif de vidange
automatique, laissez le tuyau obturé.
113189 Rev. A