OPERATION
Offset
Description
Control AntiLegionella Setting Tem-
82
perature
83
Control Block menu
84
Control Yutaki Forced OFF
85
Space Heating Heater Forced OFF
86
Control Communication Alarm bit
87~99
100
Status Unit Run/Stop
101
Status Mode
102
Status Circuit 1 Run/Stop
103
Status Heat. OTC 1
104
Status Cool. OTC 1
Status Circuit 1: Water heating Fix
105
Setting Temp
Status Circuit 1: Water cooling Fix
106
Setting Temp
107
Status Circuit 1: Eco mode
Status Circuit 1: Heat ECO Offset
108
Temperature
Status Circuit 1: Cool ECO Offset
109
Temperature
Status Circuit 1: Thermostat Setting
110
Temperature
Status Circuit 1: Thermostat Room
111
Temperature
Status Circuit 1: Wireless Setting
112
Temperature
Status Circuit 1: Wireless Room Tem-
113
perature
114
Status Circuit 2 Run/Stop
115
Status Heating OTC 2
116
Status Cooling OTC 2
14
PMML0351A rev.4 - 04/2020
Values
0~80
0: No
1: Block (user cannot
access the menu)
0: Normal Operation
1: Forced OFF
0: Normal Operation
1: Heater Forced OFF
0: No
1: Alarm
Reserved
0: Stop
1: Run
B0: 0: Cool / 1: Heat
B1: 0: Normal / 1: Auto
0: Stop
1: Run
0: No
1: Points
2: Gradient
3: Fix
0: No
1: Points
2: Fix
0~80
0~80
0: ECO
1: Comfort
1~10
1~10
50~350 (5,0~35,0)
0~1000 (0,0~100,0)
50~350 (5,0~35,0)
0~1000 (0,0~100,0)
0: Stop
1: Run
0: No
1: Points
2: Gradient
3: Fix
0: No
1: Points
2: Fix
Read/Write
VRF
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Availability
RAC
ATW
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O