FUNCIONAMIENTO
5.2.2 Datos disponibles para HC-A(16/64)MB
Offset
Descripción
0
Existe
1
Dirección del sistema
2
Dirección de la unidad
3
Type
4
Orden de ajuste de marcha/paro
5
Orden de ajuste del modo
6
Orden de ajuste del ventilador
7
Ajuste de la temperatura
Temperature setting with 0.5°C
8
intervals
Heating temperature setting for AUTO
9
Cool/Heat
Heating Temperature setting for AUTO
10
Cool/heat with 0.5°C intervals
Cooling Temperature setting for AUTO
11
Cool/heat
Cooling Temperature setting for AUTO
12
Cool/heat with 0.5°C intervals
13
Ajuste del deflector
14
Central setting (2)
15
Estado de On/Off
16
Estado del modo
31
PMML0351A rev.4 - 04/2020
Valores
0: No exist
1: Exist
H-LINK 1: 0~15
H-LINK 2: 0~63
0: Indoor Unit
0: Stop
1: Run
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
0: Low
1: Medium
2: High
3: High2
4: Auto
ºC (set according to the unit
working range)
ºC x 10 (19.5ºC read as 195)
°C
ºC x 10 (19.5ºC read as 195)
°C
ºC x 10 (19.5ºC read as 195)
0 ~ 7 (7 is Auto)
Bit 0: On/Off (always can be
stopped)
Bit 1: Mode
Bit 2: Setting Temp
Bit 3: Fan
Bit4: Louver
0: Off
1: On
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Lectura/escritura
VRF
Lectura
O
O
Lectura
O
Lectura
O
Lectura/escritura
O
Lectura/escritura
O
Lectura/escritura
O
Lectura/escritura
O
Lectura/escritura
O
Lectura/escritura
O
Lectura/escritura
O
Lectura/escritura
O
Lectura/escritura
O
Lectura/escritura
O
Lectura/escritura
O
Lectura
O
Lectura
O
Disponibilidad
Adaptador
ATW
O
O
O
O
O
O
O
O
O
O
O