Label the system when reloading is complete.
Pay particular attention not to overload the refrigerating system.
22. Before proceeding with reloading, the system must undergo the
pressure test with OFN and the tightness test at the end of reload-
ing, but before commissioning.
It is necessary to carry out an additional tightness test before
leaving the site.
23. C ollected refrigerant must be returned to the fluid supplier in the
appropriate collection cylinder, compiling the corresponding Transfer
Note of Scraps.
DO NOT mix the refrigerants in the collection units and, in particular,
in the cylinders.
24. If the compressors or their oils must be removed, make sure they have
been emptied at an acceptable level to be sure that the flammable
refrigerant does not remain in the lubricant.
This process must be carried out before the compressor returns to
the suppliers.
Only use electric heating on the compressor body to speed up this
process.
25. Once installation is complete, check that there's no loss of refrigerant
(the refrigerating liquid produces toxic gas if exposed to a flame).
0.5 - PROPER USE
• The air-conditioner should be used for the exclusive purpose of pro-
ducing hot or cool air (on demand) for the sole purpose of obtaining
a comfortable temperature in the room.
• An improper use of the devices (external and internal) with possi-
ble damages caused to people, things or animals relieves OLIMPIA
SPLENDID from any liability.
0.6 - Hazardous zones
• The climate controllers must not be installed in environments with
the presence of inflammable gases, explosive gases, in very humid
environments (laundries, greenhouses, etc.), or in places with other
machines that generate a strong heat source, in proximity of a sources
of salt water or sulphurous water.