• In Zone 1 and Zone 2, the electronic submodule may be
inserted and removed during operation. The enclosure (Ex
e / IP 54) in which the ET 200iSP is found may only be
opened briefly for this purpose (see the "SIMATIC
Distributed I/O ET 200iSP" manual).
• In configuring the ET 200iSP, you must consider the
permissible number of electronic submodules (see the
"SIMATIC Distributed I/O ET 200iSP" manual, Chapter
3.6).
Commissioning
• The relevant national regulations must be observed when
commissioning the system.
• When checking the functionality of the equipment, observe
the EN 60079-17 guidelines. This standard includes the
regulations found in the international standard
IEC 60 079-17.
• The parallel combination of output current circuits is only
permitted for the module types:
- 4DO DC17.4V/27mA SHUT DOWN "H" / "L"
(6ES7132-7RD11-0AB0 / 6ES7132-7GD10-0AB0)
- 4DO DC17.4V/40mA SHUT DOWN "H" / "L"
(6ES7132-7RD22-0AB0 / 6ES7132-7GD21-0AB0)
and for a maximum of two power circuits which are wired in
parallel. In this case, the separately listed electronic data
on the EC special test certificate apply.
For use in the USA and Canada
The control drawing for the ET 200iSP system is
provided with the power supply module. Alternatively, you can
find the latest edition at
https://support.industry.siemens.com,
Reference A5E00455287.