RX Series
Appendix D (cont.) Relay Settings Record
Fn #
Group
Function Description
F030
Phase Rotation Trip
F031
Phase Rotation Trip Delay
F032
Phase Loss Trip and Delay
F033
Over Frequency Trip Limit
F034
Over Frequency Trip Delay
F035
Under Frequency Trip Limit
F036
Under Frequency Trip Delay
F037
Motor KW Trip
F038
Motor KW Trip Point
F039
Motor KW Trip Delay Time
F040
Power Factor Trip Range
F041
Power Factor Trip Point
F042
Power Factor Trip Delay Time
Power Factor Current
F043
Direction
Coast Down (Back Spin)
F044
Lockout Timer
F045
Maximum Starts per Hour
Minimum Time Between Starts
F046
Inhibit
- 85 - |
P a g e
Digital Solid State Protection Relay 5 - 2000A
Adjustment / Display Range
0, 1 or 2
0=Disabled, 1=ABC, 2=ACB]
1 – 20 seconds
0, 1-20 Seconds [0= Disabled]
0, 1 – 10Hz [0=Disabled]
1 – 20 seconds
0, 1 – 10Hz [0=Disabled]
1 – 20 seconds
0-2
0 = Disabled
1 = Over KW Trip
2 = Under KW Trip
20 – 100% of full load KW
1 – 999 minutes
0, 1 – 3 [0=Disabled, 1=lag,
2=lead, 3= lead/lag]
.01 – 1 (cos. Θ)
1 – 20 seconds
0 - 1, [0=Normal, 1= Reversed]
0 = Disabled, or 1 - 60 minutes
0 = Disabled, or 1 – 10 starts
0 = Disabled, or 1 - 60 minutes
Setting
Factory
Setting
Increments
Setting
1
0
1
2
1
1
1
0
1
2
1
0
1
2
1
0
1%
50 (%)
1
1
1
0
.01
.50
1
2
1
0
1 minute
0
1
0
1 minute
0
Setting