When choosing MF1, MF2 and MF4:
It.
TYPE
rs0: final.
3
rs0
rs1
rs1: restore factory settings.
11. ADVANCED PROGRAMMATION MENU
- Hold
+
for 3 seconds.
- By mean of
or
- Confirm with
and go to next step.
- Save and quit the MENU, at any time, with
- This is the parameters sequence (in bold default
values):
P01: stand-alone operation
P01
P02
P02: 2-pumps set.
Only in case of P02:
d_S: duty/stand-by operation. Pumps never
d_S
d_A
run simultaneously.
d_A: duty/assist operation with alternated
starting sequence.
Select LOCAL INPUTS (P_L) or REMOTE PRO-
P_L
P_r
BES (P_R). See 7.2.2.
AR1 Activation of the automatic restore system
AR0
ART (Ar1) o disable (Ar0). See description (*)
In case of enabled ART, it can be set the
n01
n48
number of restore attempts, between 1 and
48.
t20 It can be set the span of the attempt between
t05
10 and 40 seconds.
It can be set the overcurrent coefficient in
%. This is the percentage above the rated
C10
C30
current that is considered an overcurrent.
Factory setting is a 20% (C20).
Fast-cycling alarm (A04):
- rc0: alarm disabled.
- rc1: activated, when hammering is detec-
rc0
rc2
ted it is delayed in 5 seconds the start in
order to protect the pump.
- rc2: alarm is activated and the pump is
stopped upon detection.
Only if it has been activated the fast-cycling
alarm (rc1 or rc2) in the previous step, it can
be selected the period of time between 3
t01
t99
consecutive starts, in seconds, that will be
consider as a rapid cycle (between 1" and
99"). The default value is 10 seconds (t10).
This is the setting of the "continuous ope-
ration" timer, very useful, for example, to
prevent flooding.
The pump stops when the previously confi-
H00
H99
gured continuous operation time (in minutes)
is exceeded, showing the alarm code A30 on
the screen.
Off (H00), 1 min (H01), .... 24 min (H24).
rs0
rs1
Restore factory setting.
DESCRIPTION
values can be changed.
REACCIÓN DEL SISTEMA
(*) ART FUNCTION (Automatic Reset Test)
When the device has stopped the pump by the inter-
vention of the dry-running protection system (A01
ALARM) or minium pressure alarm (A11), the ART tries,
after 5 minutes, to start AGAIN the pump in order to
restore the water supply.
After this first attempt, are performed consecutive at-
tempts every 30 minutes.
This function can be activated in the ADVANCED
MENU. It can also be set the number of attempts (1-48)
and the span of the attempt (10-40 seconds).
.