Mechanical Installation
1. Install the pump (not included) securely to the top of the
fuel tank per the instructions included with the pump.
2. Install mounting plate to tank (if applicable for your
installation). Refer to the mounting plate "Tank Mounting"
section of the mounting plate instructions.
3. Remove the dispenser cover to allow inside access to the
bottom of the dispenser. Begin by pulling the reset knob off
its shaft. The cover is removed by unscrewing the 3 - Phillips
head screws located on the sides and back of the cabinet
(see diagram on page 9 for screw locations).
4. Place dispenser on mounting plate; using the 4 – 5/16 x 18
screws, nuts, and grommet washers, screw the dispenser
securely to the mounting plate through the 4 holes located in
the bottom of the dispenser cabinet base (Figure 1).
5. In FR902RU installations, install an Emergency Shut-Off Valve (not supplied) to the dispenser inlet. Position
valve so it can be rigidly mounted to the tank, and is not dependent on the dispenser for support.
6. Carefully measure and install pipe between the pump and Emergency Shut Off Valve. The pipe is not intended
to support the pump or the dispenser in any manner.
CAUTION
Threaded pipe joints and connections should be sealed with the appropriate sealant or
sealant tape to minimize the possibility of leaks.
Electrical Installation
WARNING
Overall dispenser installation and electrical wiring should be performed ONLY by a licensed
electrician and service personnel in compliance with local, state, and national electrical
code NEC/ANSI/NFPA 70, NFPA30, NFPA 30A, and NFPA 395 as appropriate to the intended
use of the dispenser. Threaded rigid conduit, sealed fittings, and conductor seal should be
used. The pump must be properly grounded. Improper installation or use of this dispenser
can result in serious bodily injury, or death!
CAUTION
All electrical appliances should operate at the rated nameplate voltage. Power should be
supplied to this dispenser from a dedicated circuit breaker appropriately sized to handle
the pump being used with the dispenser. No other equipment should be powered by this
circuit. Wiring must be of sufficient size to carry the correct current for the pump. Voltage
drop will vary with distance to pump and size of wire; refer to the National Electrical Code
(NEC), or local codes, for voltage drop compensation to be sure you are using the correct
size wire for your application.
fillrite.com
| 902V SERIES CABINET DISPENSER
INSTALLATION AND OPERATION MANUAL
Figure 1
4