In case of an error, LED "FAULT" would be illuminated.
The Masters box controls the operation.
Manual mode
Press [ ON/OFF ] + [ RESET ] during 3 seconds to enter manual mode. The LEDS blinks alternated.
Pressing [ ON/OFF ] alternates start or stop the motor.
Press [ RESET ] to return to automatic mode.
5) CONFIGURATION.
Adjust the ELV micro-switches according to the next tables:
For the general configuration, see the Master instructions manual.
6) START-UP
Follow the Master instructions manual.
Verify the motor rotation direction. If, in three-phase motors, it were necessary reverse the rotation direction,
reverse 2 phases in the input line.
7) PROTECTION AND ERRORS.
Code of LEDS
LED FAULT
Fast flashing 0,5 s
LED FAULT
Slow flashing 1 s
LED FAULT
Fixed
Alarms and failures
OVERCURRENT
If the current exceeds the value established in the Master, the system will
stop.
The reset is automatic. If the error is not solved, 3 new attempts are
performed every 10 seconds.
If the error is still present after the third attempt, the system will be set to a
permanent fault and LED "FAUL" is fixed.
PHASE FAILURE (only three-phase motors)
If some of the phases fall, the system will stop.
The reset is automatic. If the error is not solved, 3 new attempts are
performed every 10 seconds.
If the error is still present after the third attempt, the system will be set to a
permanent fault and LED "FAUL" is fixed.
PERMANENT FAILURE
Press [RESET] for manual reset. The sequence of attempts is reinitiated.
A) For selection of the order of operation (see the Master
instructions manual) regulate Switch 1 and 2:
SWITCH 1
SLAVE 1
OFF
SLAVE 2
OFF
SLAVE 3
ON
B) For selection of single-phase or three-phase motor,
regulate Switch 4:
SWITCH 1
SINGLE-PHASE
THREE-PHASE
- 16 -
SWITCH 2
SWITCH 3
OFF
ON
OFF
SWITCH 2
SWITCH 3
SWITCH 4
SWITCH 4
OFF
ON