8. Boiler operation and maintenance
8. Boiler operation and maintenance
Use the main switch to deactivate the boiler and wait
until the boiler cools down - min. 1 hour before
maintenance (boiler cleaning).
8.A Burner operation guidelines:
Normal daily boiler operation:
•
check the correct operation of system components: burner, control system
•
check water level on a pressure gauge
•
check fuel level and quality and fuel feed system operation
•
check hydraulic joints leak tightness
•
keep the boiler room clean and tidy.
In case of any performance issues, remove the faulty devices or contact an
Authorised Service Centre to arrange a repair or an adjustment.
8.B Inspection scope and schedule:
a) Monthly
•
check system water pressure
•
check safety valve operation
•
check control and safety device operation
•
check tightness of all connectors and joints
•
check balanced ventilation system.
b) Minor inspection (every 6 months)
•
check rope seal and gaskets,
•
check boiler door thermal insulation,
•
check safety devices (safety valve, safety temperature limiter STB etc.).
c) Major inspection (every 12 months)
•
check rope seal and gaskets,
•
check boiler door and cleanout cover thermal insulation,
•
check safety devices (safety valve, safety temperature limiter STB etc.),
•
check flue gas
•
clean combustion section of the boiler
•
check thermal insulation of the boiler
•
check and adjust burner, adjust control system settings.
After a long boiler/burner standstill, the residual oxygen in boiler water and the
oxygen from the air mixed with a carbonic acid have highly corrosive properties.
Take any precautions necessary if the boiler downtime is to exceed a week.
Experts in biomass heating
8.C Maintenance
a) Boiler, burner, fuel feed system - mechanical
Regular and correct maintenance of the boiler is essential for the correct and
reliable operation and low fuel consumption of the system. Contact an Authorised
Service Centre at least once a year and after every boiler downtime to arrange
an inspection.
Heating system maintenance procedure:
•
deactivate the boiler (system) (stop mode)
•
wait for a complete stop and allow to cool
•
reduce the boiler temperature to the level allowing safe maintenance
•
open boiler door
•
clean combustion chamber and all flues and check the rope seals in the
boiler doors (replace if necessary)
•
check and clean the burner (remove if necessary) – also, clean the motor
and fan (especially vanes) from the outside
•
close the boiler door with burner
•
remove the cover
•
clean the combustion products from the rear section of the boiler
•
check cover gasket quality (rope seals) and remove as required
•
close the rear boiler cleanout
•
check smoke duct condition and gas tightness
•
check installation and operation of the boiler sensors
•
check installation and operation of the fuel feed system
•
feeder gear motor
•
fuel feed ducts leak tightness and flow capacity.
Compact Bio / Compact Bio Luxury User Manual – EN 07.15