Adaptive ITCS Start Control
This function can be activated / deactivated via item 06 in the settings menu.
When a programme is running in
heating earlier than programmed. This function ensures the required temperature,
when the programme switches to Comfort mode. To start system heating ahead of
tie intelligently, the system executed various temperatures measurements over time.
It uses this data to estimate the ideal time to start heating, before the next palliative
Comfort set-point.
Window Open Detection
This function can be activated via item 07 in the settings menu If this function is
active, the
icon is displayed on the LCD monitor.
Questa funzione esegue una misurazione e registrazione dell' andamento della
temperatura negli ultimi 10 minuti:
Phase n°1 – window open detection: the thermostat goes into a window open
detection state (the icon and temperature reading flash) when the temperature
has dropped by at least 1,2°C over the last 10 minutes.
Phase n°2 – detection of closing or action by the user: If, over 10 minutes, the
temperature rises by 0,3°C, the window open state is cancelled. The thermostat
automatically goes back to the current mode. If this does not happen, the radiator
switches off for 30 minutes, and then goes back to the state set previously.
If the user pushes a key, the window open state is cancelled as well.
The thermostat automatically goes back to the current mode.
Calibrating the internal sensor
This function is available in item 05 of the settings menu and is used to recalibrate
the thermostat if the temperature it measures differs from that measured by another
thermometer in the home:
Maximum editable value
Steps 0,1°C
mode, it can be used to start the system
5 °C
25
EN