Descargar Imprimir esta página

PowerWalker VFI 1500 Manual De Uso página 19

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 59
 
6. Specifications 
 
MODEL 
CAPACITY* 
INPUT 
Low Line Transfer 
Voltage 
Low Line Comeback 
Range 
High Line Transfer 
High Line Comeback 
Frequency Range 
Phase 
Power Factor 
OUTPUT 
Output voltage 
AC Voltage Regulation   
Frequency Range   
(Synchronized Range) 
Frequency Range (Batt. Mode) 
Overload 
Current Crest Ratio 
Harmonic Distortion 
Transfer 
AC Mode to Batt. Mode 
Time 
Inverter to Bypass 
Waveform (Batt. Mode) 
EFFICIENCY 
AC Mode 
Battery Mode 
BATTERY 
Battery Type 
Numbers 
Standard 
Recharge Time 
Model 
Charging Current   
Charging Voltage   
Battery Type & Numbers 
Long‐run 
Charging Current   
Model 
Charging Voltage 
PHYSICAL 
Tower 
Dimension, D X W X H   
Case 
Net Weight (kgs) 
Dimension, D X W X H   
Rack Case 
Net Weight (kgs) 
ENVIRONMENT 
Operation Humidity 
Noise Level 
MANAGEMENT 
Smart RS‐232 or USB 
Optional SNMP 
* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 208VAC. 
 
www.powerwalker.com 
1000 
1000 VA / 800 W 
1500 VA / 1200 W 
160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % or 80 VAC / 70 VAC / 60 VAC / 50 VAC ± 5 %   
( based on load percentage 100% ‐ 80 % / 80 % ‐ 70 % / 70 ‐ 60 % / 60 % ‐ 0)   
≧ 0.99 @ 220‐230 VAC or 110‐120 VAC 
208/220/230/240VAC or 110/115/120/127 VAC 
110%‐130%: UPS shuts down in 30 seconds at battery mode or transfers to bypass mode 
>130%: UPS shuts down immediately at battery mode or transfer to bypass mode when 
≦ 3 % THD (Linear Load)               
≦ 6 % THD (Non‐linear Load) 
~ 85% 
12 V / 7 AH 
12 V / 9 AH 
4 hours recover to 90% capacity (Typical) 
41.0 VDC ± 1%   
Depending on the capacity of external batteries 
41.0 VDC ± 1%   
397 X 145 X 220 (mm) 
13 
14 
420x438x88[2U] (mm) 
16 
10 
17 
20‐90 % RH @ 0‐ 40°C (non‐condensing) 
Supports Windows® 98/2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix and MAC 
Power management from SNMP manager and web browser 
Page 18
1500 
2000 
2000 VA / 1600 W 
  175 VAC ± 5 % or 85 VAC ± 5 %   
  300 VAC ± 5 % or 150 VAC ± 5 %   
  290 VAC ± 5 % or 145 VAC ± 5 %   
40Hz ~ 70 Hz 
Single phase with ground 
± 3% (Batt. Mode) 
47 ~ 53 Hz or 57 ~ 63 Hz 
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz 
100%~110%: audible warning 
when the utility is normal. 
the utility is normal. 
3:1 
≦ 4 % THD (Linear Load)                 
≦ 7 % THD (Non‐linear Load) 
Zero 
4 ms (Typical) 
Pure Sinewave 
~ 83% 
12 V / 7 AH 
1.0 A(max.) 
4.0 A or 8.0 A(max.) 
421 X 190 X 318 (mm) 
26 
580x438x133[3U] (mm) 
10 
29 
Less than 45dBA @ 1 Meter 
3000 
3000 VA / 2400 W 
~ 88% 
12 V / 9 AH 
82.1 VDC ±1%   
82.1 VDC ±1%   
13 
28 
13 
17 
31 
17 

Publicidad

loading

Este manual también es adecuado para:

Vfi 1000Vfi 2000Vfi 3000