Schnittstellen
IP-Adresse ..................................................................... manuell 192.168.0.5
Netzmaske .............................................................................. 255.255.255.0
Geräteadresse BS-Bus .................................................................................. 1
Sonstiges
Sprache ..............................................................................................Deutsch
Inbetriebnahmeassistent ........................................................................... an
Technische Daten
Isolationskoordination (IEC 60664-1/IEC 60664-3)
Bemessungsspannung ....................................................................... 1000 V
Überspannungskategorie (OVC) ................................................................. III
Bemessungs-Stoßspannung (IEC 60664-1) ............................................. 8 kV
Bemessungsisolationsspannung (IEC 60664-1) .................................. 1000 V
Spannungsprüfung, Stückprüfung (IEC 61010-1) ........................... AC 2,2 kV
Versorgungsspannung
Klemme A1/+, A2/– ......................................................... AC/DC 24...240 V
Klemme X1 ........................................................................................DC 24 V
Überwachtes IT System
Tensión nominal U
..........................................AC 0...690 V, DC 0...1000 V
n
U
für UL Anwendungen ..................................................... AC/DC 0...600 V
n
Ansprechwerte
Ansprechwert R
(Alarm 1) ....................................................1 kΩ...10 MΩ
an1
Ansprechwert R
(Alarm 2) ...................................................1 kΩ...10 MΩ
an2
Messkreis
Messspannung U
.......................................... profilabhängig, ±10 V, ±50 V
m
Messstrom I
................................................................................... ≤403 μA
m
Innenwiderstand R
, Z
......................................................................≥124 kΩ
i
i
Zulässige Fremdgleichspannung U
Zulässige Netzableitkapazität C
..........................................................................profilabhängig, 0...1000 μF
Schaltglieder
Kontaktdaten nach IEC 60947-5-1
Gebrauchskategorie ............. AC-13 / AC-14 / DC-12 / DC-12 / DC-12 / DC-12
Bem.betriebsspannung ................230 V / 230 V / 24 V / 48 V / 110 V / 220 V
Bem.betriebsstrom ................................... 5 A / 3 A / 1 A / 1 A / 0,2 A / 0,1 A
Bemessungsisolationsspannung ≤2000 m NN .................................... 250 V
Bemessungsisolationsspannung ≤3000 m NN ..................................... 160 V
Minimale Kontaktbelastbarkeit ................................. 1 mA bei AC/DC ≥10 V
Sonstiges
EMV .........................................................................................IEC 61326-2-4
Schutzart Einbauten (DIN EN 60529) ...................................................... IP40
Schutzart Klemmen (DIN EN 60529) ...................................................... IP20
Entwicklung unter Beachtung folgender Normen: ........................................
isoxx685(W)-x-x ................................................................... DIN EN 61557-8
isoxx685(W)-x-P ................................................................. DIN EN 61557-9
14
iso685-x_D00022_12_Q_INTE/12.2023
............................................... ≤1200 V
fg
...................................................................
e
Interfaces
IP adress......................................................................... manual 192.168.0.5
Network mask ......................................................................... 255.255.255.0
Adress BS bus ............................................................................................... 1
Other
Language ...........................................................................................German
Commissioning wizard ............................................................................... on
Technical data
Insulation co-ordination (IEC 60664-1/IEC 60664-3)
Rated voltge ....................................................................................... 1000 V
Overvoltage category (OVC) ........................................................................ III
Rated impulse voltage (IEC 60664-1) ..................................................... 8 kV
Rated insulation voltage (IEC 60664-1) .............................................. 1000 V
Voltage test, routine test (IEC 61010-1) ......................................... AC 2.2 kV
Supply voltage
Terminal A1/+, A2/– ........................................................ AC/DC 24...240 V
Terminal X1 ........................................................................................DC 24 V
Sistema IT vigilado
Nominal system voltage U
..............................AC 0...690 V, DC 0...1000 V
n
U
for UL applications .......................................................... AC/DC 0...600 V
n
Response values
Response value R
(Alarm 1) ..................................................1 kΩ...10 MΩ
an1
Response value R
(Alarm 2) ..................................................1 kΩ...10 MΩ
an2
Measuring circuit
Measuring voltage U
...............................profile dependent, ±10 V, ±50 V
m
Measuring current I
...................................................................... ≤ 403 μA
m
Internal resistance R
, Z
................................................................... ≥ 124 kΩ
i
i
Permissible extraneous DC voltage U
Permissible system leakage capacitance C
..........................................................dependent on the profile, 0...1000 μF
Switching elements
Contact data acc. to IEC 60947-5-1
Utilisation category .............. AC-13 / AC-14 / DC-12 / DC-12 / DC-12 / DC-12
Rated op. voltage .........................230 V / 230 V / 24 V / 48 V / 110 V / 220 V
Rated op. current. ..................................... 5 A / 3 A / 1 A / 1 A / 0.2 A / 0.1 A
Rated insulation voltage ≤2000 m NN ................................................. 250 V
Rated insulation voltage ≤3000 m NN ................................................ 160 V
Minimum contact rating .............................................. 1 mA at AC/DC ≥10 V
Other
EMC .........................................................................................IEC 61326-2-4
Degree of protection, built-in components (DIN EN 60529) .................... IP40
Degree of protection, terminals (DIN EN 60529) ..................................... IP20
Developed in compliance with the following standards: ...............................
isoxx685(W)-x-x ................................................................... DIN EN 61557-8
isoxx685(W)-x-P ................................................................. DIN EN 61557-9
............................................ ≤ 1200 V
fg
....................................................