Troubleshooting
The UPS control panel lights will turn on in the sequences below to signal that the UPS is having
operational difficulties.
Lights (On/Flashing) and Condition
On: REPLACE BATT
Condition: Replace Battery
On: BATT LOW, ON BATT
Condition: Battery Low
On: BYPASS, LINE, LOAD, OVERLOAD
Condition: On Bypass due to Overload
Flashing: OVERLOAD
Condition: Short Circuit
On: FAULT
Condition: Wiring Fault
On: FAULT, 100%
Condition: Battery Voltage too High
On: FAULT, BYPASS, LINE, 50%
Condition: On Bypass due to High
Output Voltage
On: FAULT, BYPASS, LINE
Flashing: 50%
Condition: On Bypass due to Low
Output Voltage
On: FAULT, BYPASS, LINE, 25%
Condition: On Bypass due to High Bus
Voltage
On: FAULT, BYPASS, LINE
Flashing: 25%
Condition: On Bypass due to Low Bus
Voltage
On: BYPASS, LINE
Flashing: FAULT
Condition: On Bypass due to High
Internal Temperature
Flashing: LINE
Condition: Input Abnormal
On: FAULT, 50%
Flashing: LINE
Condition: No Output due to High
Output Voltage and Abnormal Input
17-05-032-932471.indb 13
Solution
Let the UPS system charge for at least 12 hours
and perform a self test using the "ON/Test
Switch" as described in the Basic Operation
section. If the light continues to stay on, contact
Tripp Lite for service.
Prepare for imminent UPS shutdown.
Reduce the load the UPS supports.
Remove the cause of the short circuit from the
UPS output.
Check the utility line for wiring problems, such as
reversed line and neutral or a missing ground.
Restart the UPS. If the problem persists, contact
Tripp Lite for repairs.
Restart the UPS. If the problem persists, contact
Tripp Lite for repairs.
Restart the UPS. If the problem persists, contact
Tripp Lite for repairs.
Restart the UPS. If the problem persists, contact
Tripp Lite for repairs.
Restart the UPS. If the problem persists, contact
Tripp Lite for repairs.
Check the UPS to be sure that there is adequate
space for air to circulate near the vents and that
the fan is working properly. Restart the UPS.
This indicates that utility power is too high or low
for the UPS to operate in BYPASS mode, so if an
inverter failure occurs, the UPS will deliver no
output.
Restart the UPS. If the problem persists, contact
Tripp Lite for repairs.