Descargar Imprimir esta página

Liberty Pumps LCU-15 Manual De Instalación página 4

Bombas de condensación
Ocultar thumbs Ver también para LCU-15:

Publicidad

Idiomas disponibles

Idiomas disponibles

If unit is mounted in an unheated area that is exposed to
temperatures below freezing, the unit and lines must be drained
to prevent damage to the pump.
Pump models have sealed permanently lubricated bearings and
require no additional lubrication.
Troubleshooting
No repair work shall be carried out during the warranty period
without prior factory approval. Liberty Pumps, Inc. assumes no
responsibility for damage or injury due to disassembly in the field.
Dismantling the pump voids the warranty. Servicing the pump
other than simple cleaning of pump inlet or impeller should be
referred to the factory or its authorized service centers.
Pump Does Not Run or Hum
1.
Line circuit breaker may be off, tripped or loose. Have a
certified electrician check fuse or breaker.
2.
Water level in tank may be too low to activate switch.
Add more water to tank.
3.
Plug on power cord may not be making contact in
receptacle. Check security and connection.
4.
Float may be obstructed. Make sure float is free and not
interfering with the inlet pipe or any other obstruction.
5.
Pump is installed on a non-level surface. Re-level pump.
6.
Consult factory.
Pump Runs or Hums But Does Not Deliver Water
1.
Check valve may be installed incorrectly or is defective.
Check that it is installed properly.
2.
Examine discharge tubing for any kinks or blockages.
Check that intake tubing or pipe is not obstructed.
3.
Discharge line may be blocked or frozen. Check to see if
line passes through cold areas or is blocked.
4.
Inlet of pump is plugged or the impeller is jammed.
Remove the pump screen and clean inlet and impeller.
5.
Vertical lift is beyond pumps capability. Refer to chart for
pump's maximum lift capability. Note: At the pump's
maximum lift there will be no flow.
Model
Max. Recommended Lift
LCU-15
LCU-15S
LCU-20S
LCU220S
LCU-SP20
LCU-SP220S
Pump Runs and Removes Water But Does Not Shut Off
1.
Float is stuck in the "on" position. Check to make sure the
float is free to move up and down without obstruction.
2.
Pump is installed on a non-level surface. Level the pump.
3.
Switch is defective. Consult factory.
Pump Runs But Delivers Very Little Water
1.
Vertical lift is approaching the pump's maximum lift
capability. Refer to maximum lift chart.
4 | EN
Max. Lift
12'
15'
17'
20'
17'
20'
Copyright © Liberty Pumps, Inc. 2020 All rights reserved.
2.
Pump's inlet is partially blocked. Check that inlet is clear
of debris.
3.
Discharge line is partially blocked. Check line for
blockage.
4.
Check valve is not opening all the way. Check for
defective or blocked check valve.
Circuit Breaker Trips or Fuse Blows When Pump Starts
1.
Fuse or breaker size is too small. Use a 15-amp breaker.
2.
Other major appliances are on the same circuit. Pump
must be on its own circuit.
3.
Pump is connected to an extension cord or wiring is
inadequate. Have a certified electrician check for proper
wiring.
4.
Defective motor or switch. Consult factory.
Warranty
Liberty Pumps Wholesale Products Limited
Warranty
Liberty Pumps, Inc. warrants that Liberty Pumps wholesale
products are free from all factory defects in material and
workmanship for a period of three (3) years from the date of
purchase (excluding batteries). The date of purchase shall be
determined by a dated sales receipt noting the model and serial
number of the pump. The dated sales receipt must accompany the
returned pump if the date of return is more than three years from
the date of manufacture noted on the pump nameplate.
The manufacturer's sole obligation under this Warranty shall be
limited to the repair or replacement of any parts found by the
manufacturer to be defective, provided the part or assembly is
returned freight prepaid to the manufacturer or its authorized
service center, and provided that none of the following
warranty-voiding characteristics are evident:
The manufacturer shall not be liable under this Warranty if the
product has not been properly installed, operated, or maintained
per manufacturer instructions; if it has been disassembled,
modified, abused, or tampered with; if the electrical cord has been
cut, damaged, or spliced; if the pump discharge has been reduced
in size; if the pump has been used in water temperatures above
the advertised rating; if the pump has been used in water
containing sand, lime, cement, gravel, or other abrasives; if the
product has been used to pump chemicals, grease, or
hydrocarbons; if a non-submersible motor has been subjected to
moisture; or if the label bearing the model and serial number has
been removed.
Liberty Pumps, Inc. shall not be liable for any loss, damage, or
expenses resulting from installation or use of its products, or for
indirect, incidental, and consequential damages, including costs of
removal, reinstallation or transportation.
There is no other express warranty. All implied warranties,
including those of merchantability and fitness for a particular
purpose, are limited to three years from the date of purchase.
This Warranty contains the exclusive remedy of the purchaser,
and, where permitted, liability for consequential or incidental
damages under any and all warranties are excluded.
7196000G