Required Tools for Installation
Phillips screwdriver
4 mm
(5/32 in.) hexagonal
Level
wrench
Scale
Flare tool for RA10A
Utility knife or scissors
Gauge manifold for R410A
Torque wrench
Vacuum
pump for R410A
Wrench (or spanner)
Charge hose for R410A
Pipe cutter with reamer
1. BEFORE INSTALLATION
1-1. THE FOLLOWING
SHOULD ALWAYS
BE OBSERVED
FOR SAFETY
*
Be sure to read "THE FOLLOWING
SHOULD
ALWAYS
BE OBSERVED
FOR SAFETY" before installing the air conditioner.
*
Be sure to observe the warnings and cautions specified here as they include important items related to safety.
*
After reading this manual,
be sure to keep it together with the OPERATING
INSTRUCTIONS
for future reference.
PNT
ite)
. BEFORE INSTALLATION
OUTDOOR UNIT INSTALLATION
. FLARING WORK AND PIPE CONNECTION... cccccetetriees
. PURGING PROCEDURES, LEAK TEST, AND TEST RUN..
. RELOCATION AND MAINTENANCE ou... ccc ceeeteereneriens
4
2.
3
4
5
(Could lead to death, serious Injury, etc.)
Do not install the unit by yourself (user).
Incomplete installation could cause fire or electric shock, injury due to the unit
falling, or leakage of water. Consult the dealer from whom
you purchased the
unit or a qualified installer.
@ Perform the installation securely referring to the installation manual.
Incomplete installation could cause fire or electric shock, injury due to the unit
falling, or leakage of water.
& When
installing the unit, use appropriate protective equipment and tools
for safety.
Failure to do so could cause injury.
& Install the unit securely in a place which can bear the weight of the unit.
If the installation location cannot bear the weight of the unit, the unit could fall
causing injury.
& Perform electrical work according to the installation manual
and be sure
to use an exclusive circuit. Do not connect other electrical appliances to
the circuit.
If the capacity of the power circuit is insufficient or there is incomplete electri-
cal work, it could result in a fire or an electric shock.
Do
not damage
the wires by applying excessive
pressure with parts or
screws.
Damaged
wires could cause fire.
@ Be sure to cut off the main
power in case of setting up the indoor P.C.
board or wiring works.
Failure to do so could cause electric shock.
Use the specified wires to connect the indoor and outdoor units secure-
ly and attach the wires firmly to the terminal block connecting
sections
so the stress of the wires is not applied to the sections.
Incomplete connecting and securing could cause fire.
@ Do not install the unit in a place where inflammable gas may leak.
If gas leaks and accumulates
in the area around
the unit, it could cause an
explosion.
& Do not use intermediate connection
of the power cord or the extension
cord and do not connect many devices to one AC outlet.
It could cause
a fire or an electric shock due to defective contact, defective
insulation, exceeding the permissible current, etc.
@ Be sure to use the parts provided or specified
parts for the installation
work,
The use of defective parts could cause an injury or leakage of water due to a
fire, an electric shock, the unit falling, etc.
@ When
plugging the power supply plug into the outlet, make sure that there
is no dust, clogging, or loose parts in both the outlet and the plug. Make
sure that the power supply plug is pushed completely into the outlet.
If there is dust, clogging, or loose parts on the power supply plug or the outlet,
it could cause electric shock or fire. If loose parts are found on the power sup-
ply plug, replace it.
PU or Uy gle)
@ Depending
on the installation area, install a Ground
Fault Interrupt (GFI)
circuit breaker.
If the Ground
Fault Interrupt (GFI) circuit breaker is not installed, an electric
shock could occur.
@ Perform
the drainage/piping work securely according
to the installation
manual.
If there is defect in the drainage/piping work, water could drop from the unit,
soaking and damaging
household goods.
Use appropriate tools and piping materials for installation.
& When
pumping
down
the refrigerant, stop the compressor
before dis-
@ When
installing the unit, securely connect the refrigerant pipes before
@ Fasten a flare nut with a torque wrench as specified in this manual.
@ The
unit shall
be installed
in accordance
with
national wiring
regula-
@ Ground the unit correctly.
(Could lead to serious injury in particular environments when operated incorrectly.)
@ Do not touch the air inlet or the aluminum fins of the outdoor unit.
@ Do not install the outdoor unit where small animals may live.
@ Attach the electrical cover to the indoor unit and
the service
panel to
the outdoor unit securely.
lf the electrical cover of the indoor unit and/or the service panel of the out-
door unit are not attached
securely,
it could
result in a fire or an electric
shock due to dust, water, etc.
@ When
installing,
relocating,
or servicing
the unit,
make
sure that no
substance
other than
the specified
refrigerant
(R410A)
enters the re-
frigerant circuit.
Any
presence
of foreign substance
such
as air can cause
abnormal
pres-
sure rise and
may
result in explosion or injury. The
use of any refrigerant
other than that specified for the system will cause
mechanical failure, sys-
tem
malfunction,
or unit breakdown.
In the worst case, this could lead to a
serious impediment to securing product safety.
@ Do
not discharge
the
refrigerant
into the atmosphere.
If refrigerant
leaks during installation, ventilate the room.
If refrigerant comes in contact with a fire, harmful gas could be generated. Re-
frigerant leakage may cause suffocation. Ventilate the room.
@ Check that the refrigerant gas does not leak after installation has been
completed.
lf refrigerant gas leaks indoors, and comes
into contact with the flame of a
fan heater, space heater, stove, etc., harmful substances will be generated.
The pressure of R410A
is 1.6 times more than R22.
Not using appropriate
tools or materials and incomplete installation could cause the pipes to burst
or injury.
connecting the refrigerant pipes.
lf the refrigerant pipes are disconnected
while the compressor
is running
and the stop valve is open, air could be drawn in and the pressure in the re-
frigeration cycle could become abnormally high. This could cause the pipes
to burst or injury.
starting the compressor.
lf the compressor is started before the refrigerant pipes are connected and
when
the stop valve is open, air could be drawn
in and the pressure in the
refrigeration
cycle could
become
abnormally
high.
This could
cause
the
pipes to burst or injury.
lf fastened too tight, a flare nut may break after a long period and cause re-
frigerant leakage.
tions.
Do
not connect the ground
to a gas
pipe, water pipe,
lightning
rod or tel-
ephone ground. Defective grounding could cause electric shock.
This could cause injury.
If small animals
enter and
touch
the electric parts inside the unit, it could
cause a malfunction, smoke emission, or fire. Also, advise user to keep the
area around the unit clean.
1-2. SPECIFICATIONS
Power supply
Pipe length and height difference *1, *2, *3, "4, *5, *6
Model
Rated Voltage |
Frequency
Max. pipe length per indoor
Max. height difference *7
Max.
no. of bends per in-
Refrigerant adjustment A
unit / for multi-system
door unit / for multi system
8
MXZ-3B24NA
MXZ-3B30NA
208 / 230 V
60 Hz
25 m (82 ft) / 70 m (230 ft)
15 m (49 ft)
25/70
20 g/m (1.08 oz each 5 ft)
MXZ-4B36NA
*4 Never
use
pipes with thickness
less than specified.
The
pressure
resist-
ance will be insufficient.
*2 Use a copper pipe or a copper-alloy seamless pipe.
*3 Be careful not to crush or bend the pipe during pipe bending.
*4 Refrigerant pipe bending radius must be 100 mm
(4 in.) or more.
*5 Insulation material : Heat resisting foam plastic 0.045 specific gravity
*6 Be sure to use the insulation of specified thickness.
Excessive
thickness
may cause incorrect installation of the indoor unit and insufficient thickness
may cause dew drippage.
En-1
*7 If the outdoor unit is installed higher than the indoor unit, max. height differ-
ence is reduced to 10 m (33 ft).
*8 If pipe length exceeds 40 m (1371 ft), additional refrigerant (R410A) charge
is required.
(No additional
charge
is required for pipe length
less than
40 m (131 ft).)
Additional refrigerant (m) = A * (pipe length (m) — 40)
Additional refrigerant (ft) = A x
P i p e len * ft) — 131