6.5 Electrical protection
The power supply for the heat pump must come, preferably, from an exclusive circuit with regulatory
protection components (30mA differential protection) and a magneto-thermal switch.
- The electrical installation must be carried out by a specialized professional (electrician) in accordance with
the standards and regulations in force in the country of installation.
- The heat pump circuit must be connected to a safety earth circuit at the terminal block.
- The cables must be properly installed to prevent interference.
- The pump is intended for connection to a general power supply with earth connection.
- Section of the cable; This section is indicative and should be checked and adapted according to the needs
and conditions of use.
- The tolerance of acceptable voltage variation is +/- 10% during operation.
The connections must be dimensioned according to the power of the device and the state of
installation.
Models
EVOTOP INVERBOOST 05
EVOTOP INVERBOOST 06
EVOTOP INVERBOOST 09
EVOTOP INVERBOOST 12
EVOTOP INVERBOOST 16
EVOTOP INVERBOOST 20
EVOTOP INVERBOOST 25
EVOTOP INVERBOOST 25T
EVOTOP INVERBOOST 30
EVOTOP INVERBOOST 30T
These values are given as a guideline, only the intervention of an authorized technician
can determine the values corresponding to your installation.
The electric line must be equipped with a ground connection and with a circuit breaker with
difference 30mA in head.
6.
6.
6.
Electrical
Electrical
Electrical
Circuit
breaker
2,5 mm²
7 A
84 m
7 A
84 m
10 A
57 m
13 A
43 m
16 A
34 m
20 A
29 m
26 A
135 m
9 A
105 m
34 A
21 m
13 A
-
- 26 -
Wiring
Wiring
Wiring
Maximum length of the wire
4 mm²
135 m
135 m
90 m
68 m
54 m
45 m
210 m
160 m
34 m
27 m
6 mm²
10 mm²
200 m
335 m
200 m
335 m
130 m
225 m
100 m
170 m
80 m
135 m
66 m
110 m
315 m
525 m
240 m
400 m
49 m
84 m
39 m
68 m