Descargar Imprimir esta página

Riello RG2 Instrucciones De Instalación, Uso Y Mantenimiento página 19

Quemadores de gasóleo

Publicidad

Idiomas disponibles

Idiomas disponibles

4.10 Maintenance position
There are two ways to access the nozzle, the diffuser disc and
the electrodes:
1st Method (Fig. 12):
 remove the wires 4) from the flame control, the flame sen-
sor 5) and unscrew the nut 3) from the pump.
 Loosen the screws 2) and extract the nozzle-holder assem-
bly 1) by turning to the right.
 Remove the wires 4) from the electrodes, loosen the screw
3)(Fig. 11) and remove the diffuser disc-holder assembly 7)
from the nozzle-holder assembly 1).
 Screw on the nozzle 6) while holding the nozzle holder still
with a spanner.
 Refit following the operations in the reverse order to the one
described above.
2
4
5
6
3
Installation
1
7
E9317
Fig. 12
17
2nd Method (Fig. 13):
 unscrew and remove the fixing nut to the flange and remove
the burner from the boiler.
 Connect the burner to flange 1), loosen the screws 3) then
remove the blast tube unit 2).
 Remove the wires 4) from the electrodes.
 Replace and correctly screw in the nozzle 6), tightening it as
shown in Fig. 13.
 Refit following the operations in the reverse order to the one
described above.
Having put back the nozzle-holder assembly,
screw in the nut 9), as shown in Fig. 14.
WARNING
2
5
4
S9698
Tighten
without
bringing
right
to the end stop
GB
3
6
1
Fig. 13
9
Fig. 14
20136866
D5684

Publicidad

loading

Este manual también es adecuado para:

Rg337377543739354