Descargar Imprimir esta página

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

Electrical Accessories
For MUH, HUHAA, Dayton 804RZ6 thru 804RZ9, and
804T01 thru 804T22 Series Unit Heaters
INSTALLATION OF INTERNAL THERMOSTAT MT1,
MT2, 2E569, 3UG72, 2YU33, 2YU95, and 810VA9
1. Remove 5/16" (7.9mm) knockout from back of heater and route cap-
illary tube through hole (Figure 1).
2. Install thermostat bulb clip in slot provided in the back panel of the
heater. Secure capillary bulb in clip.
3. Press on left side of logo label on front of heater to locate shaft and
screw holes. Punch holes through label.
4. Install thermostat as shown in Figure 2, coiling any excess capillary
tubing inside the heater.
Figure 1. Installation of Internal Thermostat Capillary
WARNING
TO PREVENT POSSIBLE ELECTRICAL SHORT CIRCUIT OR
FIRE, KEEP CAPILLARY TUBING AWAY FROM INTERNAL
ELECTRICAL COMPONENTS.
5. Refer to wiring diagram, Figure 6, for wiring procedure on 3KW and
5KW (208V, 240V and 277V only). Refer to wiring diagram, Figure
7, for wiring procedure on all other heaters.
6. CAUTION: To prevent a possible fire or damage to heater, if a two
stage thermostat is provided, it MUST be wired so Stage 1 turns the
rear heating element (where fan control is located) on first and off
last. Stage 2 MUST turn on elements other than the rear element as
the need for additional heat is required and will turn on last and off
first. Remove backing from label (supplied) and install over
thermostat shaft. Install knob by pushing onto the thermostat shaft.
Figure 2. Installation of Internal Thermostat
INSTALLATION OF FAN SWITCH
FS, 3UG03 and 2YU82
1. Remove 1/2" (12.7mm) knockout (located between ON and AUTO)
from back of heater (Figure 3).
2. Install manual fan switch as shown in Figure 3. (Note orientation of
slot in switch nozzle. Locate slot in the switch nozzle towards the
"AUTO" position.) Be sure to use lockwasher to prevent rotation of
switch.
Figure 3. Installation of Fan Switch
ECR 02780
3. Install leads to terminal block. Refer to wiring diagram, Figure 6, for
wiring procedure on 3KW and 5KW units (208V, 240V, and 277V
only). Refer to wiring diagram, Figure 7, for wiring procedure on all
other heaters.
INSTALLATION OF REMOTE FAN SWITCH
The Remote Fan Switch is mounted external and remote from the unit
heater. The voltage of the remote fan switch circuit is the same as the
supply voltage to the heater.
1. Use 14 gauge copper, NEC Class 1, 600V rated insulated wire.
Wiring must meet all local and NEC requirements.
2. Install the remote fan switch in a standard wall box in any conve-
nient location that is protected from traffic or other accidental dam-
age.
3. Connect the 14 gauge copper field wire to the switch lead wires with
suitable connectors.
4. A 1/2-inch (12.7mm) knockout is provided in the back of the heater
adjacent to the control terminal board. Use a crimp-on terminal suit-
able for No. 8 screw on the control terminal board. Connect one field
wire terminated lead to terminal F1 and the other terminated lead to
terminal F2. Refer to Figure 6 for connecting to heaters without built-
in contactors. Refer to Figure 7 for connecting to heaters equipped
with built-in contactors.
INSTALLATION OF REMOTE PILOT DUTY FAN
SWITCH RFS2 (Including Wall Switch and Relay)
The Remote Fan Switch is mounted external and remote from the unit
heater.
1. Use 18 gauge (min.), NEC Class 1, 600V wiring that meets all local
and NEC requirements.
2. Install the remote fan switch in a standard wall box in any conve-
nient location that is protected from traffic or other accidental dam-
age.
3. Connect the field wire to the switch lead wires with suitable connec-
tors.
4. A 1/2-inch (12.7mm) knockout is provided in the back of the heater
adjacent to the control terminal board. Use a crimp-on terminal
suitable for No. 8 screw on the control terminal board. Connect one
field wire terminated lead to terminal "R" and the other terminated
field wire lead to terminal "G". Refer to Figure 7.
5. Install relay as indicated below.
INSTALLATION OF FAN RELAY (For RFS2)
1. Mount relay in control compartment with two No. 8 mounting screws
as shown in Figure 4.
2. Connect the lead wires from the relay to the control terminal board
as shown in Figure 7. Each lead wire is marked for proper terminal
location; connect the lead wires as indicated.
Figure 4. Installation of Fan Relay
8/23
RFS1
5200-11261-001

Publicidad

loading

Resumen de contenidos para Marley MT1

  • Página 1 Electrical Accessories For MUH, HUHAA, Dayton 804RZ6 thru 804RZ9, and 804T01 thru 804T22 Series Unit Heaters INSTALLATION OF INTERNAL THERMOSTAT MT1, 3. Install leads to terminal block. Refer to wiring diagram, Figure 6, for MT2, 2E569, 3UG72, 2YU33, 2YU95, and 810VA9 wiring procedure on 3KW and 5KW units (208V, 240V, and 277V only).
  • Página 2 INSTALLATION OF HEAT RECOVERY THERMOSTAT HEAT RECOVERY THERMOSTAT HRTA 2-STAGE HRTA, 3UG63 and 2YU90 REMOTE SUMMER FAN SWITCH RFS1 INTERNAL THERMOSTAT SUMMER FAN SWITCH FS (MANUAL) BLACK NOTE: This accessory cannot be installed on heaters equipped TO H1 with built-in single-pole or two-stage thermostats, because they use the same mounting location (see item 5 below).
  • Página 3 Notes / Notas / Notes...
  • Página 4 Para Calentadores de Unidades Para calentadores unitarios de las series MUH, HUHAA, Dayton 804RZ6 a 804R79 y 804T01 a 804T22 INSTALACION DEL TERMOSTATO INTERNO MT1, 3. Instale los conductores correspondientes al bloque terminal. Use como refer- MT2, 2E569, 3UG72, 2YU33, 2YU95 Y 810VA9 encia el diagrama del cableado, Figura 6, para conocer el procedimiento de conexión de cables en las unidades de 3KW y 5KW (208V, 240V y 277V sola-...
  • Página 5 INSTALACION DEL TERMOSTATO DE TERMOSTATO DE RECUPERACION DE CALOR RECUPERACION DE CALOR HEAT RECOVERY THERMOSTAT HRTA HRTA, 3UG03, 2YU90 2-STAGE REMOTE SUMMER FAN SWITCH RFS1 INTERRUPTOR REMOTO DEL VENTILADOR INTERNAL TERMOSTATO HRTA 3UG63 y 2YU90 DE VERANO RFS1 THERMOSTAT INTERNO DE 2 SUMMER FAN SWITCH FS (MANUAL) O INTERRUPTOR DEL VENTILADOR DE ETAPAS...
  • Página 6 Pour les aérothermes des séries MUH, HUHAA, Dayton 804RZ6 à 804R79 et 804T01 à 804T22 MONTAGE D’UN THERMOSTAT INTERNE MT1, MT2, 3. Monter les fils vers la borne serre-fils. Effectuer le câblage des 3 KW et 2E569, 3UG72, 2YU33, 2YU95 ET 810VA9 des 5 KW (208 V, 240 V et 277V seulement) conformément à...
  • Página 7 MONTAGE D’UN THERMOSTAT DE THERMOSTAT DE RÉCUPERATION DE CHALEUR HRTA RÉCUPÉRATION DE CHALEUR INTERRUPTEUR À DISTANCE HRTA, 3UG63 et 2YU90 THERMOSTAT INTERNE DU RFS1 OU INTERRUPTEUR DU À 2 NIVEAUX VENTILATEUR D'ÉTÉ FS (MANUEL) REMARQUE: On ne peut le monter sur des radiateurs équipés d’un thermostat unipolaire intégré...
  • Página 8 Notes / Notas / Notes...

Este manual también es adecuado para:

Mt22e5693ug722yu332yu95810va9