10.1 Preparation
Implement safety measures. See
u
Tools
• No special tools required.
10.2 Procedure
Disassembly is performed in reverse order to assembly. See
installation.
11 Disposal
Improper disposal will lead to pollution of the environment. Furthermore, the
materials can no longer be recycled.
Dispose of the product, the packaging and any escaping operating materials
u
in accordance with the applicable national regulations.
12 Troubleshooting
12.1 Procedure
Step 1: Check the system
In case of malfunctions, first check the system or the system part where the
u
product is installed. Check the following items:
• All connections
• Settings. See
g 13. Technical
Step 2: Check the product
1. Make sure the system or system part is not under pressure or voltage.
2. Check the product based on the fault patterns described below.
3. Perform troubleshooting using the information under "Remedy".
If the malfunction cannot be eliminated as described under "Remedy": Disas-
semble the product and return it. See
4. After the malfunction has been eliminated; Put the system or product back
into operation.
12.2 Malfunction types
Malfunctions of classification Info
Message
Description
Simulation active
Simulation active (output sig-
nal or process variable).
Flow low Info
Info: MBE -5 %.
Flow high Info
Info: Standard MBE +5 %.
Temperature high
Temperature too high.
Energy Counter off - Air only Medium = Air
Formula for energy counter
only stored for air, therefore
without function.
Voltage low for Q1/2
Voltage at Q1/2 too low.
Voltage low for Q2/a, Qa
Voltage at Q2/a, Qa too low.
Voltage low for IO-Link
Voltage too low for IO-Link.
Q1 Config out of Range
Switching points parameter-
ized outside the measurement
range.
Q2 Config out of Range
Switching points parameter-
ized outside the measurement
range.
Qa Config out of Range
Switching points parameter-
ized outside the measurement
range.
AVENTICS™ 652/653 | 549411-001-AD | English
g 6.2.3 Implementing safety
g 6. Assembly and
data.
g 4.3 Returning the
product.
Remedy
-
Increase MBE to the specified
value.
Reduce the standard MBE to
the specified value.
Reduce the temperature to
the specified value.
-
Adjust voltage to the specified
value.
Adjust voltage to the specified
value.
Adjust voltage to the specified
value.
Parameterize switching points
within the measuring range.
Parameterize switching points
within the measuring range.
Parameterize switching points
within the measuring range.
Malfunctions of classification Warning
Message
measures.
No MQTT Connection
Q1/2 Overtemp
Q1 Shortcut
Q2 Shortcut
Q2/a Overload
Qa Overload
Q2/a OverTemp
Qa OverTemp
Q2 PulseConfig
Flow high Warning
Pressure low
Pressure high
Temperature low
Temperature high
Invalid Medium + RefCond
Supply Voltage too low/high! Supply voltage does not corre-
Internal Temperature too
low/high!
Description
Remedy
No connection possible to the
• There is a problem in the
MQTT broker.
MQTT configuration:
Check if broker, port or au-
thentication are invalid.
• There is a problem in the
Ethernet configuration:
Check network settings.
Driver overload for switch out-
• Reduce the load on the
put Q1/Q2.
switch outputs.
• Ensure that specified val-
ues for ambient tempera-
ture are maintained.
Short circuit at Q1.
Eliminate short circuit.
Short circuit at Q2.
Eliminate short circuit.
Q2/a: No current flow.
• Check whether line is
properly connected.
Qa: No current flow.
• Check whether load resis-
tance is too high.
Q2/a: Overtemperature of the
• Ideal: load of 500 Ω
output driver.
• Check whether ambient
temperature is too high.
Qa: Overtemperature of the
output driver.
Implausible configuration of
• Reduce pulse width.
the Q2 pulse output.
• Increase pulse value.
Warning: Extended MBE +5 %. Reduce the extended MBE to
the specified value.
Pressure too low.
Increase pressure.
Pressure too high.
Reduce pressure.
Temperature too low.
Increase the temperature to
the specified value.
Temperature too high.
Reduce the temperature to
the specified value.
RefCond only valid for air.
Adjust medium or parameteri-
zation of RefCond.
Adjust voltage to the specified
spond to the specified value.
value.
Internal temperature does not
Adjust temperature to the
correspond to the specified
specified value.
value.