8. Technical data
Main features
Rated power
Active power
Technology
IN/OUT Configuration
Neutral system
Bypass
Overvoltage category
Input electrical characteristics
Rated input voltage
Range of input voltages
Input frequency
Max input current (with minimum input
voltage and battery charger active)
Power factor on input
Total harmonic distortion of the input current
Inrush current
Icp Presumed short circuit current
Electrical output characteristics (normal mode)
Rated output voltage
Rated output frequency
Tolerance on the output frequency
Max output current
Crest factor admitted on the output current
Total harmonic distortion of output voltage
on linear rated load
Total harmonic distortion of output voltage
on non-linear rated load
Network efficiency (online mode)
Efficiency in ECO MODE
Overload admitted
WHAD HE 3-4-5-6 kVA
3 101 66
3 101 67
3000 VA
4000 VA
3000 W
4000 W
on-line double conversion
Classification according to EN62040-3: VFI-SS-111
Single-phase / Single-phase
Neutral passing straight from input to output (not isolated)
Automatic (static)
Manual (for maintenance - optional)
OVC II
3 101 66
3 101 67
230 V
184 V – 264 V with rated load
50 / 60 Hz ± 2% (autosensing)
50 / 60 Hz ± 14% (by software configuration)
18 A
24 A
PF > 0,99
THDi < 3% (full load)
100% of the rated current
10 kA
3 101 66
3 101 67
230 V ± 1%
50 / 60 Hz
synchronised with the input (with a range of ± 2% to ± 14%,
selected through the software)
± 1% when not synchronised
13 A
17,3 A
3:1
< 0,5%
< 3%
up to 96%
99% max (by software configuration)
125% for 10 minutes without automatic bypass activation
150% for 60 seconds without automatic bypass activation
3 101 68
3 101 69
5000 VA
6000 VA
5000 W
6000 W
3 101 68
3 101 69
30 A
35 A
3 101 68
3 101 69
21,7 A
26 A
31