IO-Link-specific
19 (0x13) Product ID
20 (0x14) Product text
21 (0x15) Serial number
22 (0x16) Hardware version
23 (0x17) Firmware version
24 (0x18) Application-specific
marking
36 (0x24) Device status
40 (0x28) Input process data
AVENTICS specific
Index dec
Name
Format
(hex)
(offset)
64 (0x40) Sensor-specific
String
name
66 (0x42) System status
UInt
190
OpTimer
UInt
(0xBE)
260
Q1 mode
UInt
(0x104)
262
Q1 type
UInt
(0x106)
270
Q1 set switching
Float
(0x10E)
point 1
271
Q1 set switching
Float
(0x10F)
point 2
272
Q1 unit and
String
(0x110)
range
278
Q1 polarity
UInt
(0x116)
279
Q1 simulation
UInt
(0x117)
switch output
291
Q2 function
UInt
(0x123)
292
Q2 type
UInt
(0x124)
AVENTICS™ IO-Link AF2 | R412027828-BAL-001-AC | English
String
64 bytes
ro
R412026761
R412026762
R412026763
String
64 bytes
ro
Air flow sensor
String
16 bytes
ro
String
64 bytes
ro
String
64 bytes
ro
String
32 bytes
rw
***
UInt
8 bits
ro
0 = device is OK
1 = maintenance re-
quired
2 = outside of speci-
fication
3 = function test
4 = error
5...255 = reserved
PD In
32 bytes
ro
Lengt
Ac-
Default value
h
cess
32
rw
***
bytes
8 bits
ro
0 = Ok
1 = warning of error
2 = error
32 bits ro
Operating time in seconds [s]
8 bits
rw
0 = switch output hysteresis volume
flow
1 = switch output window function
volume flow
2 = switch output hysteresis pressure
3 = switch output window function
pressure
4 = switch output hysteresis temper-
ature
5 = switch output window function
temperature
8 bits
rw
2 = NPN
3 = PNP
4 = DRV/push-pull
4
rw
- 30.0 ... 999
bytes
9.0
4
rw
- 30.0 ... 999
bytes
9.0
32
ro
Unit and range for index 270 and 271
bytes
8 bits
rw
0 = make contact
1 = break contact
8 bits
rw
255
8 bits
rw
0
8 bits
rw
2 = NPN
3 = PNP
4 =
DRV/push-pull
AVENTICS specific
Index dec
Name
(hex)
299
Q2 switch mode UInt
(0x12B)
300
Q2 set switching
(0x12C)
point 1
301
Q2 set switching
(0x12D)
point 2
302
Q2 switch out-
(0x12E)
put unit and
range
307
Q2 switch out-
(0x133)
put simulation
308
Q2 switch out-
(0x134)
put polarity
Value
Com-
range
ment
309
Qa pulse output
[unit]
(0x135)
unit and range
310
Q2 pulse valence Float
(0x136)
311
Q2 pulse width
(0x137)
312
Q2 pulse mode
(0x138)
313
Q2 upper fre-
(0x139)
quency value
314
Q2 lower fre-
(0x13A)
quency value
315
Q2 frequency
(0x13B)
unit and range
316
Q2 maximum
(0x13C)
frequency
317
Q2 minimum
(0x13D)
frequency
318
Q2 frequency
(0x13E)
simulation
See index 272
See index 272
319
Q2 frequency
(0x13F)
mode
380
Qa analog mode UInt
(0x17C)
0 = inactive
383
Qa analog polar-
(0x17F)
ity
1 = active
255 = normal
384
Qa upper analog
(0x180)
value (20mA)
0 = switch output
1 = frequency
385
Qa lower analog
(0x181)
value (4mA)
2 = pulse output
3 = analog output
386
Qa analog signal
(0x182)
unit and range
for switch, pulse
and frequency
390
Qa analog signal
output
(0x186)
in case of error
Format
Lengt
Ac-
Default value
(offset)
h
cess
8 bits
rw
0 = switch output hysteresis volume
flow
1 = switch output window function
volume flow
2 = switch output hysteresis pressure
3 = switch output window function
pressure
4 = switch output hysteresis temper-
ature
5 = switch output window function
temperature
Float
4
rw
- 30.0 ... 999
bytes
9.0
Float
4
rw
- 30.0 ... 999
bytes
9.0
String
32
ro
Unit and range for index 300 and 301
bytes
UInt
8 bits
rw
255
UInt
8 bits
rw
0 = make contact
1 = break contact
String
32
ro
Unit and range for index 310
bytes
4
rw
0.001 ... 10
bytes
0.0
UInt
32 bits rw
1 ... 2000
UInt
8 bits
rw
0 = volume
1 = energy
Float
4
rw
-30.0 ... 999
bytes
9.0
Float
4
rw
- 30.0 ... 999
bytes
9.0
String
32
ro
Unit and range for index 313 and 314
bytes
UInt
16 bits rw
0 ... 10000
UInt
16 bits rw
0 ... 10000
UInt
8 bits
rw
255
UInt
8 bits
rw
0 = volume flow
8 bits
rw
0 = 4-20mA volume flow
1 = 4-20mA pressure
2 = 4-20mA temperature
UInt
8 bits
rw
0 = normal
1 = inverted signal
Float
4
rw
- 30.0...999
bytes
9.0
Float
4
rw
- 30.0...999
bytes
9.0
String
32
ro
Unit and range for index 384 and 385
bytes
UInt
8 bits
rw
0 = 3.5mA
1 = 21.5mA
Value
Com-
range
ment
[unit]
See index 302
See index 302
0 = inactive
1 = active
255 = normal
See index 309
[ms]
See index 315
See index 315
[Hz]
[Hz]
0 = 1Hz
1 = 10Hz
2 = 100Hz
3 = 1kHz
4 = 10kHz
255 = simulation
off
See index 386
See index 386
10

Publicidad

loading

Este manual también es adecuado para:

Aventics 652Aventics 653