4
READINGS MENU
To access the menu from the main template using the arrow keys
N.
Code
L00
tuA
L01
tiA
L02
tsb
L03
tGP
L04
tAE
L05
HP
L06
BP
L07
tEr
L08
SAb
L09
CP
L10
HC0
L11
SP0
L12
rEL
L13
Set
L14
dCP
L15
dCP
L16
Po
L17
Cor
L18
Uo
L19
UoB
L20
HSt
L21
dFo
L22
dHt
L23
ASP
L24
MF In
Summary of the configurator code set on the machine:
Language selection template:
, scroll down or up to reach the screen shown below:
Name
Water Outlet Temperature
Water Inlet Temperature
Coil temperature
Discharge refrigerant temperature
External air temperature
Delivery pressure
Suction pressure
Thermostat
Safety band on force-off
CP times
Operating hours
Pick-ups
Release
Current setpoint
DCP setpoint
DCP band
Power fraction
Inverter Current
Inverter outlet voltage
Bus voltage
Inverter dissipater temperature
Value of the dynamic Force-Off
DHW remote probe value
Compressor intake probe value
Multi-function input value
Output temperature (in °C) from the water consumption read by the SUW NTC 10k probe
Input temperature (in °C) to the water consumption read by the SIW NTC 10k probe
Input temperature (in °C) read by the SS NTC 10k probe in the condensation battery
Temperature (in °C) read by the SGP probe on force gas
Temperature (in °C) read by the SAE NTC 10k probe
Bar pressure read by the compressor delivery transducer
Bar pressure read by the compressor pressure suction transducer
It displays the percentage of power required by the thermostat on the basis of the
proportional/integral algorithm
Low water con tent control algorithm. This parameter indicates the temperature threshold
for re-starting the compressor
Compressor times. This display shows the time to the start or to the stop of the compressor
This screen shows the hours of operation for the compressor
This display shows the number of pick-ups carried out by the compressor
This display shows the software version
It displays the setpoint used when the machine is operating: it includes the possible
corrections of the room temperature (if this function is active)
Pressure setpoint used for condensation control
Pressure differential used when checking the condensation
Power fraction: this reading shows how much power is currently supplied to the machine
Current (in A) measured from the inverter module
Output voltage (in V) measured from the inverter module
BUS voltage (in V) measured from the inverter module
Heat dissipator temperature (in C°) of the inverter module
Current dynamic Force-Off value calculated on the basis of the outdoor air temperature
Value read by the remote probe, located in the water accumulation of the system
Temperature read by the compressor suction probe
Temperature or Volts, depending on the configuration of the multi-function input
(parameter N11)
Meaning
19