Ex-DI 4xNAMUR
In general, pulling or plugging modules is not allowed in Zone 2. Before starting work,
make sure that there is no explosive atmosphere or that the power supply is switched
off.
For repairs, you must send the I/O module to the manufacturing location. The repair
may only be carried out there.
For use in the USA and Canada
The control drawing for the ET 200SP HA and the ET 200SP is supplied with the
respective power supply module.
The latest edition can also be found at
https://support.industry.siemens.com/cs/ww/com/
(https://support.industry.siemens.com/cs/ww/en/)
Technical specifications
Ex-DI 4xNAMUR
Supply voltage
Type of supply voltage
Input current
Current consumption (rated value)
Current consumption, max.
Encoder supply
Number of outputs
Output voltage (DC)
Short-circuit protection
Power loss
Power loss, typ.
Ex(i) characteristic values
Maximum values for terminals for gas
group IIC
Uo (output no-load voltage), max.
I
(short-circuit current), max.
o
P
(output power), max.
o
14
DC supply via Ex-PM-E
50
mA
55
mA
4
8.2
V
Yes
1.2
W
9.6
V
61
mA
Valid for up to 4 electric
circuits connected in
parallel
145
mW
Valid for up to 4 electric
circuits connected in
parallel
Ex-DI 4xNAMUR