Assembly
• Check the electronic submodule for damage. Only connect
undamaged electronic submodules to the terminal module.
• The first time that an electronic submodule is inserted, the
coding element on the terminal submodule will snap in,
which prevents the insertion of an incorrect submodule.
This mechanical coding may not be changed.
• In Zone 1 and Zone 2, the electronic submodule may be
inserted and removed during operation. The enclosure (Ex
e / IP 54) in which the ET 200iSP is found may only be
opened briefly for this purpose (see the SIMATIC
Distributed I/O ET 200iSP manual).
• In configuring the ET 200iSP, you must consider the
permissible number of electronic submodules (see the
SIMATIC Distributed I/O ET 200iSP manual, Chapter 3.6).
Commissioning
• The relevant national regulations must be observed when
commissioning the system.
• When checking the functionality of the equipment, observe
the EN 60079-17 guidelines. This standard includes the
regulations found in the international standard
IEC 60 079-17.
For use in the USA and Canada
The control drawing for the ET 200iSP system is
provided with the power supply module. Alternatively, you can
find the latest edition at
https://support.industry.siemens.com
Reference A5E00455287.