9.
Specifications
Parameter
Load Rating
Maximum Load Inrush Energy
Surge Let-through Voltage (6000 Volt Surge)
UL 1449 Adjunct Classification Test Results
Maximum Applied Surge Voltage
Maximum Applied Surge Current
Maximum Applied Surge Energy
Endurance (C62.41-1991 category B3 pulses)
EMI/RFI Filter
Under-Voltage Auto Shutdown
Over-Voltage Auto Shutdown
Delay Time per Bank
Voltmeter Accuracy
Remote Control Input
Auxiliary Relay Contact Rating
Contact Closure Max Resistance
12V DC Output Max Current
Dimensions
Weight
Temperature Range:
Humidity Range
Agency Listings
* 1.2 x 50 microsecond industry standard combination wave surge as per IEEE C62.41
*CAUTION: Do not install this device if there is not at least 10 meters (30 feet) or more between the electrical
outlet and the electrical service panel.
© SurgeX | Technical Support: 800-645-9721 | surgex.com
Normal mode (50Ω load)
Common Mode (50Ω load)
Voltage
Current Draw
SEQ
SEQ-1U
SEQ
SEQ-1U
SEQ/SEQ-1U
Specification
20 Amps at 120 Volts
1400 Joules total during power-up
0 Volts
1000 Surges, 6000 Volts, 3000 Amps, B3 pulse;
measured suppressed voltage, 170 Volts; no failures
6000 Volts *
Unlimited (due to current limiting) *
Unlimited (due to current limiting) *
1 KV > 500,000; 3 KV > 10,000; 6 KV > 1000
> 30 dB 100 KHz - 50 MHz
> 20 dB
1 MHz - 50 MHz
Adjustable from 90V to 110V
Adjustable from 130V to 150V
1 – 40 seconds in 1 second increments
± 2%
5 – 30 VDC
4 mA Maximum
30V DC at 1A
100 Ω
40 mA
19" W x 10.5" D x 3.5" H
19" W x 12.25" D x 1.75" H (1 RU)
16 lb.
13 lb.
5C to 35C
0% to 95% R.H. Non-condensing
UL 1449 3
Edition (SEQ-1U Pending)
rd
UL 1283 5
Edition (SEQ-1U Pending)
th
CSA C22.2 No.8-M1986 (R2008) (SEQ-1U Pending)
User Manual
Software Version 2.0
(2 RU)
Page 23