Notices for installation
• The mounting rack of the outdoor unit shall be fastened with
expansion bolt.
• Ensure the secure installation regardless of what type of wall
on which it is installed, to prevent potential dropping that could
hurt people.
• Be sure to use the rated voltage and air conditioners dedicated
circuit far the power supply, and the power cable diameter must
meet the national requirements.
• When the maximum current of air conditioner is � 16A, it must use
the air switch or leakage protection switch equipped with
protection devices.
• The operating range is 90%-110% of the local rated voltage.But
insufficient power supply malfunction, electrical shock, or fire.
lf the voltage instability, proposed to increase the voltage regulator.
• The minimum clearance between the air conditioner and the
combustibles is 1.5 m.
• The interconnection cord connect the indoor and outdoor units. You
must first choose the right cable size befare preparing it far
connection.
• Cable Types: Outdoor Power Cable: H0?RN-F or H05RN-F;
• Minimum Cross-Sectional Area of Power cable and interconnection
cord.
North America
Appliance
Amps(A)
10
13
18
25
30
40
• The size of the interconnection cord, power cable, fuse, and
switch needed is determined by the maximum current of the unit
The maximum current is indicated on the nameplate located on
the side panel of the unit. Refer to this nameplate to choose the
right cable, fuse, or switch.
• Note: Core number of cable refer to the detailed wiring diagram
adhered on the unit which you purchased.
www.infiniton.es
Electrical Safety Requirements
lnterconnection cord: H0?RN-F or H05RN-F;
Rated Current
AWG
of Appliance(A)
18
>3 and:,; 6
16
>6 and ::;10
14
> 10 and ::;16
12
> 16 and ::;25
10
> 25 and :,;32
8
> 32 and :,;40
©@
0th
er ea1ons
R
Nominal Cross-
Sectional Area(mm
- 16 -
·
2
)
0.75
1
1.5
2.5
4
6