TX707HB
EN
Quick Start Guide
HMI – TX707HB
Additional documents
Besides this document the following material can be found on the Internet at
www.turck.com:
Data sheet
Instructions for use for TX... series
Declarations of conformity (current version)
For your safety
Intended use
The HMIs (Human Machine Interfaces) of the TX700 family are used to control,
operate and monitor machine processes. The high brightness versions of the
TX700 series are designed for use in very bright environments due to their high
sunlight readability.
The device may only be used as described in these instructions.
Any other use is not in accordance with the intended use. Turck accepts no li-
ability for any resulting damage.
General safety notes
The device may only be assembled, installed, operated, parameterized and
maintained by professionally-trained personnel.
The device meets the EMC requirements for the industrial areas. When used
in residential areas, take measures to prevent radio frequency interference.
The device may only be used in accordance with applicable national and
international regulations, standards and laws.
Notes on explosion protection
Observe national and international regulations for explosion protection.
When operating the device in a hazardous area, the user must have a working
knowledge of explosion protection (IEC/EN 60079-14, etc.).
Only use the device within the permitted operating and ambient conditions
(see Certification data and conditions resulting from the Ex-approval).
This device, with the exception of the front display, is an open device and
must be installed in a housing suitable for the environment, so that the inner
part of the device is only accessible by means of a tool.
Do not disconnect devices in an ignitable atmosphere when energized.
Do not open the device when energized.
Do not remove Ethernet connections, USB devices and SD cards in an ignit-
able atmosphere.
Do not remove the battery in an ignitable atmosphere.
Switch-off the device before replacing or wiring extension modules.
Note on explosion protection (USA and Canada only)
The devices are suitable for the use in Class I, Division 2, groups A, B, C and D
(hazardous locations and non-hazardous locations).
The power, input and output (I/O) wiring has to be done in accordance with
Class I, Division 2 and in accordance with the authority having jurisdictions.
For U.S. in accordance with Article 501.10 (B) of the National Electrical Code,
NFPA 70 and for Canada in accordance with Section 18-1J2 of Canadian
Electrical Code.
Use only components that meet Class I, Division 2 certification.
Observe the conditions resulting from Ex approval for use in Zone 2 and 22.
Special conditions of use
Zone 2 (EPL Gc):
ű
The equipment shall only be used in an area of not more than pollution degree
2, as defined in IEC/EN 60664-1.
ű
The equipment shall be installed through an end-equipment enclosure
that provides a minimum ingress protection of IP54 in accordance with
EN IEC 60079-0, suitable for the applicable gas group, temperature classifica-
tion and ambient temperature range.
ű
Transient protection shall be provided that is set at a level not exceeding 140 %
of the peak rated voltage value at the supply terminals to the equipment.
Zone 22 (EPL Dc):
ű
The equipment shall be installed through an end-equipment enclosure
that provides a minimum ingress protection of IP6x in accordance with
EN IEC 60079-0, suitable for the applicable dust group, temperature classifica-
tion and ambient temperature.
Observe the permissible ambient temperature depending on the temperature
class.
Care shall be taken not to allow layers of dust to form on the graphic panel in a
way that might cause the accumulation of static charges.
The devices have only been evaluated for low risk of mechanical impact.
Product description
Device overview
See fig. 1
Functions and operating modes
The devices of the TX700 series combine control, operation and monitoring by
a CODESYS V3 PLC with integrated visualization to a complete control unit. The
CODESYS V3 control of the TX700 has the functions PROFINET controller, EtherCAT
master, EtherNet/IP scanner and Modbus TCP as well as Modbus RTU master.
Additionally the devices of the TX700 family can be used as PROFINET device,
Modbus TCP as well as Modbus RTU server.
Additional functions
Ethernet TCP/IP or UDP/IP communication
OPC-UA server and client, MQTT
Serial communication via RS232, RS485 and RS422
Installing
Mounting the device in Zone 2/Zone 22
DANGER
Explosive atmosphere
Explosion hazard due to ignitable sparks
For use in Zone 2 and Zone 22
Only mount and connect the device if no explosive atmosphere is present.
Observe the conditions resulting from Ex approval for use in Zone 2 and 22.
See fig. 2 and 3
A = TX7...
B = installation cut-out
Tighten the fastening screws until the brackets are firmly in contact with the
device. The minimum tightening torque to guarantee protection class IP66 is
130 Ncm.
Do not cover the ventilation slots in the device.
TX...
Number of fixing brackets supplied
TX707HB
4
Connecting
Connectors and slots
See fig. 4
Connector/slot
Function
1
USB ports V2.0, max. 500 mA
2
Ethernet port 2 (10/100 Mbps)
3
Ethernet port 1 (10/100 Mbps)
4
Serial interface
5
Ethernet port 0 (10/100 Mbps)
6
Power supply
7
SD card slot
8
2 extension slots for plug-in modules
NOTE
Devices of protection class III according to EN 61140 or Class 2 according to UL
standards: All connections are SELV connections.
Power supply
Connect the device to the voltage supply according to fig. 5 and 6.
DANGER
Wrong selection of power supply
Danger to life due to overvoltage and electric shock!
Only operate the device on SELV voltage sources according to the Euro-
pean standard or on Class 2 voltage sources according to the UL standard.
Grounding the device
The device has to be grounded.
Ground the device via the grounding screw on the back of the housing or via
terminal 3 on the power supply terminal.
Observe the minimum cable cross-section of 1.5 mm² for the ground connec-
tion.
© Hans Turck GmbH & Co. KG | 100015595 2024-03